← Texas

Tap water quality report

Cypress Springs Sud Pine Valley

EPA monitoring tested this supplier for 78 contaminants and detected 17. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

78
contaminants tested
17
detected
276
people served
0
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Franklin

Compliance record

No violations on file. The EPA has no formal drinking-water violations recorded for this supplier.

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
171.4 µg/L 13%
of the EPA limit 1300 µg/L
worst single sample: 187 µg/L
14/16 SYR4 2013–2017
Nitrate
70 µg/L 0.7%
of the EPA limit 10000 µg/L
14/16 SYR4 2012–2019
Bromodichloromethane
9.42 µg/L
No EPA limit set
worst single sample: 9.52 µg/L
11/11 SYR4 2012–2019
Chloroform
24.15 µg/L
No EPA limit set
worst single sample: 34.2 µg/L
11/11 SYR4 2012–2019
Dibromochloromethane
6.385 µg/L
No EPA limit set
worst single sample: 6.65 µg/L
11/11 SYR4 2012–2019
Lead
6.6 µg/L 44%
of the EPA limit 15 µg/L
worst single sample: 10 µg/L
11/16 SYR4 2013–2017
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
4/4 LCR 2023
Dichloroacetic Acid
19.78 µg/L
No EPA limit set
worst single sample: 21.4 µg/L
3/3 SYR4 2013–2019
Fluoride
138 µg/L 3.5%
of the EPA limit 4000 µg/L
worst single sample: 140 µg/L
3/3 SYR4 2013–2019
TTHM
46.61 µg/L 58%
of the EPA limit 80 µg/L
worst single sample: 48.5 µg/L
3/3 SYR4 2013–2019
Total Haloacetic Acids (HAA5)
26.88 µg/L 45%
of the EPA limit 60 µg/L
worst single sample: 28.8 µg/L
3/3 SYR4 2013–2019
Trichloroacetic Acid
5.57 µg/L
No EPA limit set
worst single sample: 5.7 µg/L
3/3 SYR4 2013–2019
Xylenes, Total
1.952 µg/L 0%
of the EPA limit 10000 µg/L
worst single sample: 1.96 µg/L
3/8 SYR4 2012–2019
Barium
43.05 µg/L 2.2%
of the EPA limit 2000 µg/L
worst single sample: 44 µg/L
2/2 SYR4 2016–2019
Dibromoacetic Acid
1.69 µg/L
No EPA limit set
worst single sample: 1.7 µg/L
2/3 SYR4 2013–2019
Nitrate-Nitrite
57.95 µg/L 0.6%
of the EPA limit 10000 µg/L
worst single sample: 59 µg/L
2/3 SYR4 2012–2015
Ethylbenzene
0.6400 µg/L 0.1%
of the EPA limit 700 µg/L
1/8 SYR4 2012–2019
61 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalArsenicAsbestosAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalBromoformChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumCombined UraniumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebEthylene DibromideEndrinGross Alpha, Excl. Radon And UGross Beta Particle ActivityHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidNitriteOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneToxapheneTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
BROWNING, NEUMAN, R
Phone
903-588-2081
Email
office@cssud.org

Frequently asked questions about Cypress Springs Sud Pine Valley

Is Cypress Springs Sud Pine Valley tap water safe to drink?

EPA monitoring detected 17 contaminants in Cypress Springs Sud Pine Valley's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Cypress Springs Sud Pine Valley's water?

EPA monitoring detected Copper, Nitrate, Bromodichloromethane, Chloroform, Dibromochloromethane, and others. The full list with the level and data source for each is above.

How many people does Cypress Springs Sud Pine Valley serve?

Cypress Springs Sud Pine Valley reports serving 276 people in Texas, per its EPA record.

Has Cypress Springs Sud Pine Valley had any water quality violations?

The EPA has no formal drinking-water violations on file for Cypress Springs Sud Pine Valley.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.