Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MR | Monitoring | Resolved | 2013-12-30 |
PFAS detected
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 183 µg/L 14% of the EPA limit 1300 µg/L | 41/51 | SYR4 | 2013–2019 |
| Nitrate | 970 µg/L 9.7% of the EPA limit 10000 µg/L | 22/22 | SYR4 | 2012–2019 |
| Lead | 4.86 µg/L 32% of the EPA limit 15 µg/L | 18/51 | SYR4 | 2013–2019 |
| Bromodichloromethane | 16.7 µg/L No EPA limit set | 8/14 | SYR4 | 2012–2019 |
| Chloroform | 29.7 µg/L No EPA limit set | 8/14 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 3.7 µg/L No EPA limit set | 8/8 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 38.2 µg/L No EPA limit set | 8/8 | SYR4 | 2012–2019 |
| Lead | 0.00065 mg/L 4.4% of the EPA limit 0.0150 mg/L | 8/8 | LCR | 2024 |
| TTHM | 53.9 µg/L 67% of the EPA limit 80 µg/L | 8/8 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 53.3 µg/L 89% of the EPA limit 60 µg/L | 8/8 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 13.1 µg/L No EPA limit set | 8/8 | SYR4 | 2012–2019 |
| Dibromochloromethane | 8.1 µg/L No EPA limit set | 6/14 | SYR4 | 2012–2019 |
| Bromoform | 3.7 µg/L No EPA limit set | 4/14 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 1100 µg/L 11% of the EPA limit 10000 µg/L | 4/4 | SYR4 | 2012–2015 |
| Nitrite | 180 µg/L 18% of the EPA limit 1000 µg/L | 3/5 | SYR4 | 2012–2017 |
| Lithium | 17.1 µg/L No EPA limit set | 3/4 | UCMR-5 | 2025 |
| Monochloroacetic Acid | 4.9 µg/L No EPA limit set | 2/8 | SYR4 | 2012–2019 |
| Arsenic | 2.5 µg/L 25% of the EPA limit 10 µg/L | 1/1 | SYR4 | 2017 |
| Barium | 204 µg/L 10% of the EPA limit 2000 µg/L | 1/1 | SYR4 | 2017 |
| Combined Uranium | 1.3 µg/L 4.3% of the EPA limit 30 µg/L | 1/1 | SYR4 | 2017 |
| Fluoride | 200 µg/L 5% of the EPA limit 4000 µg/L | 1/1 | SYR4 | 2017 |
| Gross Alpha, Excl. Radon And U | 3 pCi/L 20% of the EPA limit 15 pCi/L | 1/1 | SYR4 | 2017 |
| Selenium | 5.3 µg/L 11% of the EPA limit 50 µg/L | 1/1 | SYR4 | 2017 |
84 contaminants tested, none detected
Utility contact
Frequently asked questions about Fort Bend County Mud 143 Water View Esta
Is Fort Bend County Mud 143 Water View Esta tap water safe to drink?
EPA monitoring detected 25 contaminants in Fort Bend County Mud 143 Water View Esta's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Fort Bend County Mud 143 Water View Esta's water?
EPA monitoring detected Copper, Nitrate, Lead, Bromodichloromethane, Chloroform, and others. The full list with the level and data source for each is above.
How many people does Fort Bend County Mud 143 Water View Esta serve?
Fort Bend County Mud 143 Water View Esta reports serving 7,245 people in Texas, per its EPA record.
Has Fort Bend County Mud 143 Water View Esta had any water quality violations?
The EPA has 1 violation on file for Fort Bend County Mud 143 Water View Esta, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.