Compliance record
PFAS detected
| Contaminant | Max | Detection rate | Period |
|---|---|---|---|
| Pfpea | 0.0030 µg/L | 1/4 | 2025 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromodichloromethane | 17.6 µg/L No EPA limit set | 65/67 | SYR4 | 2012–2019 |
| Chloroform | 32.1 µg/L No EPA limit set | 65/67 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 32 µg/L No EPA limit set | 60/62 | SYR4 | 2012–2019 |
| TTHM | 49 µg/L 61% of the EPA limit 80 µg/L | 60/62 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 49.4 µg/L 82% of the EPA limit 60 µg/L | 60/62 | SYR4 | 2012–2019 |
| Dibromochloromethane | 11.1 µg/L No EPA limit set | 58/67 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 11.3 µg/L No EPA limit set | 58/62 | SYR4 | 2012–2019 |
| Copper | 1104.5 µg/L 85% of the EPA limit 1300 µg/L | 47/61 | SYR4 | 2013–2019 |
| Dibromoacetic Acid | 8.7 µg/L No EPA limit set | 46/62 | SYR4 | 2012–2019 |
| Lead | 25 µg/L 167% of the EPA limit, in the worst sample — 15 µg/L | 23/61 | SYR4 | 2013–2019 |
| Nitrate | 660 µg/L 6.6% of the EPA limit 10000 µg/L | 16/16 | SYR4 | 2012–2019 |
| Bromoform | 8.3 µg/L No EPA limit set | 13/67 | SYR4 | 2012–2019 |
| Lead | 0.00058 mg/L 3.8% of the EPA limit 0.0150 mg/L | 8/8 | LCR | 2025 |
| Simazine | 0.2200 µg/L 5.5% of the EPA limit 4 µg/L | 7/8 | SYR4 | 2015–2019 |
| Atrazine | 0.5100 µg/L 17% of the EPA limit 3 µg/L | 5/8 | SYR4 | 2015–2019 |
| Monochloroacetic Acid | 8.5 µg/L No EPA limit set | 5/62 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 570 µg/L 5.7% of the EPA limit 10000 µg/L | 3/3 | SYR4 | 2012–2015 |
| Barium | 71.4 µg/L 3.6% of the EPA limit 2000 µg/L | 2/2 | SYR4 | 2016–2019 |
| Cyanide | 130 µg/L 65% of the EPA limit 200 µg/L | 2/2 | SYR4 | 2014–2017 |
| Fluoride | 350 µg/L 8.8% of the EPA limit 4000 µg/L | 2/2 | SYR4 | 2014–2017 |
| Monobromoacetic Acid | 1.3 µg/L No EPA limit set | 2/62 | SYR4 | 2012–2019 |
| Lithium | 17.8 µg/L No EPA limit set | 2/4 | UCMR-5 | 2025 |
| Combined Radium (-226 And -228) | 1.5 pCi/L 30% of the EPA limit 5 pCi/L | 1/1 | SYR4 | 2015 |
| Gross Beta Particle Activity | 5 pCi/L No EPA limit set | 1/1 | SYR4 | 2015 |
84 contaminants tested, none detected
Utility contact
Frequently asked questions about Fort Bend County Mud 119
Is Fort Bend County Mud 119 tap water safe to drink?
EPA monitoring detected 25 contaminants in Fort Bend County Mud 119's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Fort Bend County Mud 119's water?
EPA monitoring detected Bromodichloromethane, Chloroform, Dichloroacetic Acid, TTHM, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.
How many people does Fort Bend County Mud 119 serve?
Fort Bend County Mud 119 reports serving 5,088 people in Texas, per its EPA record.
Has Fort Bend County Mud 119 had any water quality violations?
The EPA has no formal drinking-water violations on file for Fort Bend County Mud 119.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.