← Texas

Tap water quality report

Kingsbridge Mud

EPA monitoring tested this supplier for 109 contaminants and detected 32. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

109
contaminants tested
32
detected
8,663
people served
47
health-based violations
Water source
SWP
Ownership
Local government
Counties served
Fort Bend

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

47
health-based violations
370
violations on file
1
still open
ViolationTypeStatusPeriod
TT Health-based Unaddressed 2016-04-01
TT Health-based Resolved 2015-12-01
TT Health-based Resolved 2015-12-01
TT Health-based Resolved 2015-12-01
TT Health-based Resolved 2015-12-01
MCL Health-based Resolved 2015-04-01 → 2015-06-30
MCL Health-based Resolved 2015-04-01 → 2015-06-30
MCL Health-based Resolved 2015-04-01 → 2015-06-30
MCL Health-based Resolved 2015-04-01 → 2015-06-30
MCL Health-based Resolved 2015-04-01 → 2015-06-30

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
Pfhxa 0.0072 µg/L 7/8 2024
Pfpea 0.0064 µg/L 6/8 2024
Pfba 0.0078 µg/L 5/8 2024
PFBS 0.0032 µg/L 1/8 2024

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the single worst sample on record — over 100% is worth reading, but is not by itself a violation. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
494 µg/L 38%
of the EPA limit 1300 µg/L
148/185 SYR4 2012–2017
Lead
143 µg/L 953%
of the EPA limit, in the worst sample — 15 µg/L
93/185 SYR4 2012–2017
Bromodichloromethane
60.6 µg/L
No EPA limit set
69/69 SYR4 2012–2019
Chloroform
196 µg/L
No EPA limit set
69/69 SYR4 2012–2019
Dibromochloromethane
23.6 µg/L
No EPA limit set
62/69 SYR4 2012–2019
Dichloroacetic Acid
131.3 µg/L
No EPA limit set
62/62 SYR4 2012–2019
TTHM
284 µg/L 355%
of the EPA limit, in the worst sample — 80 µg/L
62/62 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
224 µg/L 373%
of the EPA limit, in the worst sample — 60 µg/L
62/62 SYR4 2012–2019
Trichloroacetic Acid
79.1 µg/L
No EPA limit set
60/62 SYR4 2012–2019
Dibromoacetic Acid
9.7 µg/L
No EPA limit set
40/62 SYR4 2012–2019
Nitrate
850 µg/L 8.5%
of the EPA limit 10000 µg/L
32/32 SYR4 2012–2019
Atrazine
0.3700 µg/L 12%
of the EPA limit 3 µg/L
20/24 SYR4 2012–2019
Lead
0.0010 mg/L 6.7%
of the EPA limit 0.0150 mg/L
20/20 LCR 2023
Simazine
0.3100 µg/L 7.8%
of the EPA limit 4 µg/L
15/24 SYR4 2012–2019
Bromoform
10.6 µg/L
No EPA limit set
13/69 SYR4 2012–2019
Lithium
19 µg/L
No EPA limit set
8/8 UCMR-5 2023
Nitrate-Nitrite
850 µg/L 8.5%
of the EPA limit 10000 µg/L
6/6 SYR4 2012–2015
Barium
81.6 µg/L 4.1%
of the EPA limit 2000 µg/L
5/5 SYR4 2014–2019
Fluoride
400 µg/L 10%
of the EPA limit 4000 µg/L
4/4 SYR4 2014–2017
Cyanide
150 µg/L 75%
of the EPA limit 200 µg/L
3/4 SYR4 2014–2017
Combined Radium (-226 And -228)
1 pCi/L 20%
of the EPA limit 5 pCi/L
2/2 SYR4 2014
Combined Uranium
1.4 µg/L 4.7%
of the EPA limit 30 µg/L
2/2 SYR4 2014
Gross Beta Particle Activity
5.2 pCi/L
No EPA limit set
2/2 SYR4 2014
Monobromoacetic Acid
1.9 µg/L
No EPA limit set
2/62 SYR4 2012–2019
Monochloroacetic Acid
2.9 µg/L
No EPA limit set
2/62 SYR4 2012–2019
Dalapon
6.1 µg/L 3.1%
of the EPA limit 200 µg/L
1/66 SYR4 2012–2019
Di(2-ethylhexyl) Phthalate
0.9700 µg/L 16%
of the EPA limit 6 µg/L
1/24 SYR4 2012–2019
Selenium
3.2 µg/L 6.4%
of the EPA limit 50 µg/L
1/5 SYR4 2014–2019
77 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalArsenicAsbestosBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumDichloromethaneDi(2-ethylhexyl) AdipateDinosebEthylene DibromideEndrinEthylbenzeneGross Alpha, Excl. Radon And UHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNetfosaaNfdhaNmefosaaNitriteOxamylPfdaPfdoaPfeesaPfhpaPfhpsPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpesPftaPftrdaPfunaPentachlorophenolPicloramStyreneTetrachloroethyleneThallium, TotalTolueneToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
SHINDLER, ROBERT C.
Phone
713-237-1221

Frequently asked questions about Kingsbridge Mud

Is Kingsbridge Mud tap water safe to drink?

EPA monitoring detected 32 contaminants in Kingsbridge Mud's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Kingsbridge Mud's water?

EPA monitoring detected Copper, Lead, Bromodichloromethane, Chloroform, Dibromochloromethane, and others. The full list with the level and data source for each is above.

How many people does Kingsbridge Mud serve?

Kingsbridge Mud reports serving 8,663 people in Texas, per its EPA record.

Has Kingsbridge Mud had any water quality violations?

The EPA has 370 violations on file for Kingsbridge Mud, of which 47 are health-based (a contaminant limit or required treatment was breached) and 1 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.