← Texas

Tap water quality report

Fort Bend County Mud 2

EPA monitoring tested this supplier for 108 contaminants and detected 26. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

108
contaminants tested
26
detected
6,819
people served
0
health-based violations
Water source
SWP
Ownership
Local government
Counties served
Fort Bend

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

0
health-based violations
1
violations on file
0
still open
ViolationTypeStatusPeriod
MR Monitoring Resolved 1992-07-01 → 1993-06-30

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
6:2 Fts 0.0075 µg/L 1/3 2025
Pfba 0.0060 µg/L 1/3 2025
Pfpea 0.0030 µg/L 1/3 2025

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the single worst sample on record — over 100% is worth reading, but is not by itself a violation. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Bromodichloromethane
16.6 µg/L
No EPA limit set
64/64 SYR4 2012–2019
Chloroform
31.7 µg/L
No EPA limit set
64/64 SYR4 2012–2019
Dibromochloromethane
10.9 µg/L
No EPA limit set
64/64 SYR4 2012–2019
Dichloroacetic Acid
32.3 µg/L
No EPA limit set
62/62 SYR4 2012–2019
TTHM
50.6 µg/L 63%
of the EPA limit 80 µg/L
62/62 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
50.7 µg/L 85%
of the EPA limit 60 µg/L
62/62 SYR4 2012–2019
Trichloroacetic Acid
11.6 µg/L
No EPA limit set
61/62 SYR4 2012–2019
Dibromoacetic Acid
7.9 µg/L
No EPA limit set
54/62 SYR4 2012–2019
Copper
180 µg/L 14%
of the EPA limit 1300 µg/L
38/62 SYR4 2013–2019
Bromoform
5.4 µg/L
No EPA limit set
20/64 SYR4 2012–2019
Lead
25.6 µg/L 171%
of the EPA limit, in the worst sample — 15 µg/L
16/62 SYR4 2013–2019
Nitrate
570 µg/L 5.7%
of the EPA limit 10000 µg/L
16/16 SYR4 2012–2019
Lead
0.00090 mg/L 6%
of the EPA limit 0.0150 mg/L
13/13 LCR 2025
Atrazine
0.3500 µg/L 12%
of the EPA limit 3 µg/L
8/11 SYR4 2012–2019
Monochloroacetic Acid
5.8 µg/L
No EPA limit set
8/62 SYR4 2012–2019
Simazine
0.1400 µg/L 3.5%
of the EPA limit 4 µg/L
8/11 SYR4 2012–2019
Barium
90.6 µg/L 4.5%
of the EPA limit 2000 µg/L
3/3 SYR4 2016–2019
Nitrate-Nitrite
510 µg/L 5.1%
of the EPA limit 10000 µg/L
3/3 SYR4 2012–2015
Fluoride
380 µg/L 9.5%
of the EPA limit 4000 µg/L
2/2 SYR4 2014–2017
Cyanide
130 µg/L 65%
of the EPA limit 200 µg/L
1/2 SYR4 2014–2017
Combined Uranium
1.5 µg/L 5%
of the EPA limit 30 µg/L
1/1 SYR4 2017
Gross Beta Particle Activity
5.5 pCi/L
No EPA limit set
1/1 SYR4 2017
Lithium
9.06 µg/L
No EPA limit set
1/3 UCMR-5 2025
82 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalArsenicAsbestosBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebEthylene DibromideEndrinEthylbenzeneGross Alpha, Excl. Radon And UHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidNetfosaaNfdhaNmefosaaNitriteOxamylPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpesPftaPftrdaPfunaPentachlorophenolPicloramSeleniumStyreneTetrachloroethyleneThallium, TotalTolueneToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
KELLEY, PAM
Phone
713-860-6400

Frequently asked questions about Fort Bend County Mud 2

Is Fort Bend County Mud 2 tap water safe to drink?

EPA monitoring detected 26 contaminants in Fort Bend County Mud 2's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Fort Bend County Mud 2's water?

EPA monitoring detected Bromodichloromethane, Chloroform, Dibromochloromethane, Dichloroacetic Acid, TTHM, and others. The full list with the level and data source for each is above.

How many people does Fort Bend County Mud 2 serve?

Fort Bend County Mud 2 reports serving 6,819 people in Texas, per its EPA record.

Has Fort Bend County Mud 2 had any water quality violations?

The EPA has 1 violation on file for Fort Bend County Mud 2, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.