← Texas

Tap water quality report

City of La Grange

EPA monitoring tested this supplier for 109 contaminants and detected 30. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

109
contaminants tested
30
detected
4,973
people served
106
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Fayette

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

106
health-based violations
139
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2022-01-01 → 2022-03-31
MCL Health-based Resolved 2022-01-01 → 2022-03-31
MCL Health-based Resolved 2022-01-01 → 2022-03-31
MCL Health-based Resolved 2022-01-01 → 2022-03-31
MCL Health-based Resolved 2021-07-01 → 2021-09-30
MCL Health-based Resolved 2021-07-01 → 2021-09-30
MCL Health-based Resolved 2021-07-01 → 2021-09-30
MCL Health-based Resolved 2021-07-01 → 2021-09-30
MCL Health-based Resolved 2020-01-01 → 2020-03-31
MCL Health-based Resolved 2020-01-01 → 2020-03-31

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
Pfba 0.0104 µg/L 1/8 2024

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the single worst sample on record — over 100% is worth reading, but is not by itself a violation. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
348 µg/L 27%
of the EPA limit 1300 µg/L
178/208 SYR4 2013–2018
Lead
216 µg/L 1440%
of the EPA limit, in the worst sample — 15 µg/L
119/208 SYR4 2013–2018
Bromodichloromethane
28.6 µg/L
No EPA limit set
80/80 SYR4 2012–2019
Bromoform
124 µg/L
No EPA limit set
80/80 SYR4 2012–2019
Dibromochloromethane
56.6 µg/L
No EPA limit set
80/80 SYR4 2012–2019
Chloroform
11.1 µg/L
No EPA limit set
75/80 SYR4 2012–2019
Nitrate
470 µg/L 4.7%
of the EPA limit 10000 µg/L
74/80 SYR4 2012–2019
TTHM
138 µg/L 173%
of the EPA limit, in the worst sample — 80 µg/L
48/48 SYR4 2012–2019
Dibromoacetic Acid
15.1 µg/L
No EPA limit set
47/48 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
23.9 µg/L 40%
of the EPA limit 60 µg/L
47/48 SYR4 2012–2019
Dichloroacetic Acid
5.7 µg/L
No EPA limit set
43/48 SYR4 2012–2019
Trichloroacetic Acid
3.5 µg/L
No EPA limit set
42/48 SYR4 2012–2019
Lead
0.0013 mg/L 8.8%
of the EPA limit 0.0150 mg/L
17/17 LCR 2024
Arsenic
12 µg/L 120%
of the EPA limit, in the worst sample — 10 µg/L
14/23 SYR4 2012–2019
Nitrate-Nitrite
180 µg/L 1.8%
of the EPA limit 10000 µg/L
14/14 SYR4 2012–2015
Barium
67.5 µg/L 3.4%
of the EPA limit 2000 µg/L
12/12 SYR4 2013–2019
Fluoride
1200 µg/L 30%
of the EPA limit 4000 µg/L
10/10 SYR4 2014–2017
Monobromoacetic Acid
1.8 µg/L
No EPA limit set
8/48 SYR4 2012–2019
Lithium
105 µg/L
No EPA limit set
8/8 UCMR-5 2024
Selenium
8.7 µg/L 17%
of the EPA limit 50 µg/L
7/12 SYR4 2013–2019
Gross Beta Particle Activity
13.2 pCi/L
No EPA limit set
6/6 SYR4 2014–2017
Combined Radium (-226 And -228)
4.4 pCi/L 88%
of the EPA limit 5 pCi/L
5/5 SYR4 2014–2017
Gross Alpha, Excl. Radon And U
6 pCi/L 40%
of the EPA limit 15 pCi/L
3/6 SYR4 2014–2017
Chromium
1.73 µg/L 1.7%
of the EPA limit 100 µg/L
2/12 SYR4 2013–2019
Combined Uranium
9.6 µg/L 32%
of the EPA limit 30 µg/L
2/6 SYR4 2014–2017
Xylenes, Total
4 µg/L 0%
of the EPA limit 10000 µg/L
2/32 SYR4 2012–2019
Antimony, Total
0.2540 µg/L 4.2%
of the EPA limit 6 µg/L
1/12 SYR4 2013–2019
Ethylbenzene
0.6000 µg/L 0.1%
of the EPA limit 700 µg/L
1/32 SYR4 2012–2019
Thallium, Total
0.2420 µg/L 12%
of the EPA limit 2 µg/L
1/12 SYR4 2013–2019
79 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAsbestosAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebEthylene DibromideEndrinHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonochloroacetic AcidNetfosaaNfdhaNmefosaaNitriteOxamylPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneTolueneToxapheneTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
DOCKERY, JANEIRO, D
Phone
979-968-3127
Email
SUNSETWATERUTILITIES@GMAIL.COM

Frequently asked questions about City of La Grange

Is City of La Grange tap water safe to drink?

EPA monitoring detected 30 contaminants in City of La Grange's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in City of La Grange's water?

EPA monitoring detected Copper, Lead, Bromodichloromethane, Bromoform, Dibromochloromethane, and others. The full list with the level and data source for each is above.

How many people does City of La Grange serve?

City of La Grange reports serving 4,973 people in Texas, per its EPA record.

Has City of La Grange had any water quality violations?

The EPA has 139 violations on file for City of La Grange, of which 106 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.