Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Archived | 1984-12-18 → 1985-12-17 |
| MCL | Health-based | Archived | 1979-05-03 → 1980-05-02 |
| MCL | Health-based | Archived | 1979-05-03 → 1979-06-02 |
| MR | Monitoring | Resolved | 2025-12-30 |
| MR | Monitoring | Resolved | 2025-12-30 |
| RPT | Monitoring | Unaddressed | 2025-07-02 |
| MR | Monitoring | Resolved | 2010-07-01 → 2010-09-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 334 µg/L 26% of the EPA limit 1300 µg/L
worst single sample: 550 µg/L | 31/31 | SYR4 | 2013–2019 |
| Nitrate | 89.2 µg/L 0.9% of the EPA limit 10000 µg/L | 16/16 | SYR4 | 2012–2019 |
| Bromodichloromethane | 3.8775 µg/L No EPA limit set
worst single sample: 4.4 µg/L | 12/12 | SYR4 | 2012–2019 |
| Bromoform | 17.66 µg/L No EPA limit set
worst single sample: 20.3 µg/L | 12/12 | SYR4 | 2012–2019 |
| Dibromochloromethane | 12.41 µg/L No EPA limit set
worst single sample: 13.4 µg/L | 12/12 | SYR4 | 2012–2019 |
| Lead | 0.0022 mg/L 15% of the EPA limit 0.0150 mg/L | 10/10 | LCR | 2025 |
| Lead | 3.014 µg/L 20% of the EPA limit 15 µg/L
worst single sample: 3.77 µg/L | 9/31 | SYR4 | 2013–2019 |
| Dibromoacetic Acid | 3.8 µg/L No EPA limit set
worst single sample: 4.1 µg/L | 7/7 | SYR4 | 2012–2019 |
| TTHM | 34.83 µg/L 44% of the EPA limit 80 µg/L
worst single sample: 36.9 µg/L | 7/7 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 19.21 µg/L 32% of the EPA limit 60 µg/L
worst single sample: 21.1 µg/L | 7/7 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 14.44 µg/L No EPA limit set
worst single sample: 15.1 µg/L | 4/7 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 75.9 µg/L 0.8% of the EPA limit 10000 µg/L
worst single sample: 76 µg/L | 3/3 | SYR4 | 2012–2015 |
| Barium | 14.8 µg/L 0.7% of the EPA limit 2000 µg/L
worst single sample: 15 µg/L | 2/2 | SYR4 | 2015–2018 |
| Chloroform | 1.385 µg/L No EPA limit set
worst single sample: 1.4 µg/L | 2/12 | SYR4 | 2012–2019 |
| Chromium | 2.195 µg/L 2.2% of the EPA limit 100 µg/L
worst single sample: 2.2 µg/L | 2/2 | SYR4 | 2015–2018 |
| Dichloroacetic Acid | 1.19 µg/L No EPA limit set
worst single sample: 1.2 µg/L | 2/7 | SYR4 | 2012–2019 |
| Fluoride | 1609.5 µg/L 40% of the EPA limit 4000 µg/L
worst single sample: 1610 µg/L | 2/2 | SYR4 | 2014–2017 |
| Trichloroacetic Acid | 1.95 µg/L No EPA limit set
worst single sample: 2 µg/L | 2/7 | SYR4 | 2012–2019 |
| Cyanide | 20.6 µg/L 10% of the EPA limit 200 µg/L | 1/2 | SYR4 | 2014–2017 |
| Combined Radium (-226 And -228) | 1 pCi/L 20% of the EPA limit 5 pCi/L | 1/1 | SYR4 | 2012 |
| Selenium | 1.3 µg/L 2.6% of the EPA limit 50 µg/L | 1/2 | SYR4 | 2015–2018 |
| Xylenes, Total | 0.5600 µg/L 0% of the EPA limit 10000 µg/L | 1/5 | SYR4 | 2015–2019 |
57 contaminants tested, none detected
Utility contact
Frequently asked questions about City of Honey Grove
Is City of Honey Grove tap water safe to drink?
EPA monitoring detected 22 contaminants in City of Honey Grove's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in City of Honey Grove's water?
EPA monitoring detected Copper, Nitrate, Bromodichloromethane, Bromoform, Dibromochloromethane, and others. The full list with the level and data source for each is above.
How many people does City of Honey Grove serve?
City of Honey Grove reports serving 2,192 people in Texas, per its EPA record.
Has City of Honey Grove had any water quality violations?
The EPA has 7 violations on file for City of Honey Grove, of which 3 are health-based (a contaminant limit or required treatment was breached) and 1 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.