Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MR | Monitoring | Archived | 2026-01-01 → 2026-01-31 |
| MR | Monitoring | Archived | 2026-01-01 → 2026-01-31 |
| MR | Monitoring | Archived | 2026-01-01 → 2026-01-31 |
| MR | Monitoring | Archived | 2026-01-01 → 2026-01-31 |
| MR | Monitoring | Resolved | 2008-03-01 → 2008-03-31 |
| MR | Monitoring | Resolved | 2003-06-01 → 2003-06-30 |
| MR | Monitoring | Resolved | 2003-05-01 → 2003-05-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromate | 10.05 µg/L 101% of the EPA limit, at the 95th percentile of samples — 10 µg/L
worst single sample: 12 µg/L | 80/84 | SYR4 | 2013–2019 |
| Nitrate | 687.75 µg/L 6.9% of the EPA limit 10000 µg/L
worst single sample: 738 µg/L | 36/36 | SYR4 | 2012–2019 |
| Atrazine | 0.3340 µg/L 11% of the EPA limit 3 µg/L
worst single sample: 0.4300 µg/L | 27/30 | SYR4 | 2012–2019 |
| Bromodichloromethane | 12.135 µg/L No EPA limit set
worst single sample: 28.8 µg/L | 24/24 | SYR4 | 2012–2019 |
| Chloroform | 24.25 µg/L No EPA limit set
worst single sample: 26.4 µg/L | 24/24 | SYR4 | 2012–2019 |
| Dibromochloromethane | 7.663 µg/L No EPA limit set
worst single sample: 12 µg/L | 24/24 | SYR4 | 2012–2019 |
| Fluoride | 339.5 µg/L 8.5% of the EPA limit 4000 µg/L
worst single sample: 350 µg/L | 15/16 | SYR4 | 2012–2019 |
| Barium | 49.7 µg/L 2.5% of the EPA limit 2000 µg/L
worst single sample: 51 µg/L | 14/14 | SYR4 | 2013–2019 |
| Bromoform | 3.513 µg/L No EPA limit set
worst single sample: 4.8 µg/L | 14/24 | SYR4 | 2012–2019 |
| Simazine | 0.1575 µg/L 3.9% of the EPA limit 4 µg/L
worst single sample: 0.1800 µg/L | 10/30 | SYR4 | 2012–2019 |
| Copper | 10.32 µg/L 0.8% of the EPA limit 1300 µg/L
worst single sample: 11 µg/L | 9/10 | SYR4 | 2013–2017 |
| Dichloroacetic Acid | 4.86 µg/L No EPA limit set
worst single sample: 5 µg/L | 8/8 | SYR4 | 2012–2019 |
| TTHM | 44.765 µg/L 56% of the EPA limit 80 µg/L
worst single sample: 56.7 µg/L | 8/10 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 7.625 µg/L 13% of the EPA limit 60 µg/L
worst single sample: 7.8 µg/L | 8/8 | SYR4 | 2012–2019 |
| Cyanide | 152 µg/L 76% of the EPA limit 200 µg/L
worst single sample: 158 µg/L | 6/12 | SYR4 | 2014–2019 |
| Chromium | 1.45 µg/L 1.5% of the EPA limit 100 µg/L
worst single sample: 1.5 µg/L | 6/14 | SYR4 | 2013–2019 |
| Dibromoacetic Acid | 2.66 µg/L No EPA limit set
worst single sample: 2.7 µg/L | 5/8 | SYR4 | 2012–2019 |
| Arsenic | 1.5635 µg/L 16% of the EPA limit 10 µg/L
worst single sample: 1.61 µg/L | 4/14 | SYR4 | 2013–2019 |
| Di(2-ethylhexyl) Phthalate | 6.14 µg/L 102% of the EPA limit, at the 95th percentile of samples — 6 µg/L
worst single sample: 6.7 µg/L | 3/30 | SYR4 | 2012–2019 |
| Selenium | 3.095 µg/L 6.2% of the EPA limit 50 µg/L
worst single sample: 3.25 µg/L | 3/14 | SYR4 | 2013–2019 |
| Monochloroacetic Acid | 2.665 µg/L No EPA limit set
worst single sample: 2.7 µg/L | 2/8 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 1.095 µg/L No EPA limit set
worst single sample: 1.1 µg/L | 2/8 | SYR4 | 2012–2019 |
| Combined Radium (-226 And -228) | 1.5 pCi/L 30% of the EPA limit 5 pCi/L | 1/1 | SYR4 | 2015 |
| Monobromoacetic Acid | 1.8 µg/L No EPA limit set | 1/8 | SYR4 | 2012–2019 |
54 contaminants tested, none detected
Utility contact
Frequently asked questions about Utrwd Regional Water Treatment Plant
Is Utrwd Regional Water Treatment Plant tap water safe to drink?
EPA monitoring detected 24 contaminants in Utrwd Regional Water Treatment Plant's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Utrwd Regional Water Treatment Plant's water?
EPA monitoring detected Bromate, Nitrate, Atrazine, Bromodichloromethane, Chloroform, and others. The full list with the level and data source for each is above.
How many people does Utrwd Regional Water Treatment Plant serve?
Utrwd Regional Water Treatment Plant reports serving 0 people in Texas, per its EPA record.
Has Utrwd Regional Water Treatment Plant had any water quality violations?
The EPA has 7 violations on file for Utrwd Regional Water Treatment Plant, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.