Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2024-10-17 |
| TT | Health-based | Resolved | 2024-10-17 |
| TT | Health-based | Resolved | 2024-10-17 |
| TT | Health-based | Resolved | 2024-10-17 |
| TT | Health-based | Resolved | 2018-06-22 |
| TT | Health-based | Resolved | 2018-06-22 |
| TT | Health-based | Resolved | 2018-06-22 |
| MCL | Health-based | Resolved | 2010-01-01 → 2010-01-31 |
| MCL | Health-based | Resolved | 2010-01-01 → 2010-01-31 |
| MCL | Health-based | Resolved | 2010-01-01 → 2010-01-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 145 µg/L 1.5% of the EPA limit 10000 µg/L | 14/16 | SYR4 | 2012–2019 |
| Copper | 128 µg/L 9.8% of the EPA limit 1300 µg/L
worst single sample: 170 µg/L | 13/13 | SYR4 | 2012–2019 |
| Lead | 0.0018 mg/L 12% of the EPA limit 0.0150 mg/L | 6/6 | LCR | 2025 |
| Barium | 6.16 µg/L 0.3% of the EPA limit 2000 µg/L
worst single sample: 6.2 µg/L | 3/3 | SYR4 | 2012–2019 |
| Fluoride | 1153 µg/L 29% of the EPA limit 4000 µg/L
worst single sample: 1170 µg/L | 3/3 | SYR4 | 2013–2019 |
| Chromium | 4.43 µg/L 4.4% of the EPA limit 100 µg/L
worst single sample: 4.6 µg/L | 2/3 | SYR4 | 2012–2019 |
| Gross Alpha, Excl. Radon And U | 6.76 pCi/L 45% of the EPA limit 15 pCi/L
worst single sample: 6.8 pCi/L | 2/2 | SYR4 | 2016–2019 |
| Lead | 2.085 µg/L 14% of the EPA limit 15 µg/L
worst single sample: 2.1 µg/L | 2/13 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 139.875 µg/L 1.4% of the EPA limit 10000 µg/L
worst single sample: 145 µg/L | 2/3 | SYR4 | 2012–2015 |
| Bromoform | 1.33 µg/L No EPA limit set | 1/10 | SYR4 | 2012–2019 |
| Cyanide | 11.3 µg/L 5.7% of the EPA limit 200 µg/L | 1/3 | SYR4 | 2013–2019 |
| Combined Radium (-226 And -228) | 3.3 pCi/L 66% of the EPA limit 5 pCi/L | 1/3 | SYR4 | 2013–2019 |
| Dibromoacetic Acid | 2.3 µg/L No EPA limit set | 1/2 | SYR4 | 2016–2019 |
| Dibromochloromethane | 1.31 µg/L No EPA limit set | 1/10 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 2.3 µg/L 3.8% of the EPA limit 60 µg/L | 1/2 | SYR4 | 2016–2019 |
64 contaminants tested, none detected
Utility contact
Frequently asked questions about Pilot Point Rural Water Supply
Is Pilot Point Rural Water Supply tap water safe to drink?
EPA monitoring detected 15 contaminants in Pilot Point Rural Water Supply's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Pilot Point Rural Water Supply's water?
EPA monitoring detected Nitrate, Copper, Lead, Barium, Fluoride, and others. The full list with the level and data source for each is above.
How many people does Pilot Point Rural Water Supply serve?
Pilot Point Rural Water Supply reports serving 84 people in Texas, per its EPA record.
Has Pilot Point Rural Water Supply had any water quality violations?
The EPA has 205 violations on file for Pilot Point Rural Water Supply, of which 11 are health-based (a contaminant limit or required treatment was breached) and 9 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.