Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2024-10-17 |
| TT | Health-based | Resolved | 2024-10-17 |
| TT | Health-based | Resolved | 2024-10-17 |
| TT | Health-based | Resolved | 2024-10-17 |
| Other | Monitoring | Resolved | 2025-05-01 |
| Other | Monitoring | Resolved | 2025-05-01 |
| RPT | Monitoring | Resolved | 2024-10-17 |
| RPT | Monitoring | Resolved | 2024-10-17 |
| RPT | Monitoring | Resolved | 2024-10-17 |
| RPT | Monitoring | Resolved | 2024-10-17 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 73.005 µg/L 5.6% of the EPA limit 1300 µg/L
worst single sample: 94 µg/L | 14/15 | SYR4 | 2013–2017 |
| Lead | 4.052 µg/L 27% of the EPA limit 15 µg/L
worst single sample: 4.1 µg/L | 7/15 | SYR4 | 2013–2017 |
| Nitrate | 50 µg/L 0.5% of the EPA limit 10000 µg/L | 6/18 | SYR4 | 2012–2019 |
| Chloroform | 4.605 µg/L No EPA limit set
worst single sample: 4.8 µg/L | 4/8 | SYR4 | 2012–2019 |
| Barium | 364.9 µg/L 18% of the EPA limit 2000 µg/L
worst single sample: 366 µg/L | 3/3 | SYR4 | 2013–2019 |
| Fluoride | 656 µg/L 16% of the EPA limit 4000 µg/L
worst single sample: 660 µg/L | 3/3 | SYR4 | 2013–2019 |
| Bromodichloromethane | 3.27 µg/L No EPA limit set
worst single sample: 3.3 µg/L | 2/8 | SYR4 | 2012–2019 |
| Bromoform | 3.07 µg/L No EPA limit set
worst single sample: 3.1 µg/L | 2/8 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 11.915 µg/L No EPA limit set
worst single sample: 12.1 µg/L | 2/3 | SYR4 | 2012–2019 |
| Dibromochloromethane | 2.285 µg/L No EPA limit set
worst single sample: 2.3 µg/L | 2/8 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 5.48 µg/L No EPA limit set
worst single sample: 5.6 µg/L | 2/3 | SYR4 | 2012–2019 |
| Lead | 0.0022 mg/L 15% of the EPA limit 0.0150 mg/L | 2/2 | LCR | 2023 |
| TTHM | 13.36 µg/L 17% of the EPA limit 80 µg/L
worst single sample: 13.5 µg/L | 2/3 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 20.055 µg/L 33% of the EPA limit 60 µg/L
worst single sample: 20.5 µg/L | 2/3 | SYR4 | 2012–2019 |
| Antimony, Total | 1.3 µg/L 22% of the EPA limit 6 µg/L | 1/3 | SYR4 | 2013–2019 |
| Combined Radium (-226 And -228) | 1 pCi/L 20% of the EPA limit 5 pCi/L | 1/1 | SYR4 | 2013 |
| Gross Beta Particle Activity | 6.1 pCi/L No EPA limit set | 1/2 | SYR4 | 2013–2019 |
| Monobromoacetic Acid | 1.4 µg/L No EPA limit set | 1/3 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 20 µg/L 0.2% of the EPA limit 10000 µg/L | 1/3 | SYR4 | 2012–2015 |
| Nitrite | 20 µg/L 2% of the EPA limit 1000 µg/L | 1/4 | SYR4 | 2012–2015 |
| Selenium | 3.2 µg/L 6.4% of the EPA limit 50 µg/L | 1/3 | SYR4 | 2013–2019 |
| Trichloroacetic Acid | 1.4 µg/L No EPA limit set | 1/3 | SYR4 | 2012–2019 |
57 contaminants tested, none detected
Utility contact
Frequently asked questions about Oyster Creek Estates
Is Oyster Creek Estates tap water safe to drink?
EPA monitoring detected 22 contaminants in Oyster Creek Estates's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Oyster Creek Estates's water?
EPA monitoring detected Copper, Lead, Nitrate, Chloroform, Barium, and others. The full list with the level and data source for each is above.
How many people does Oyster Creek Estates serve?
Oyster Creek Estates reports serving 81 people in Texas, per its EPA record.
Has Oyster Creek Estates had any water quality violations?
The EPA has 42 violations on file for Oyster Creek Estates, of which 4 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.