← Texas

Tap water quality report

City of Sealy

EPA monitoring tested this supplier for 109 contaminants and detected 17. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

109
contaminants tested
17
detected
6,839
people served
1
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Austin

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

1
health-based violations
12
violations on file
0
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2016-10-14
Other Monitoring Resolved 2025-07-01
Other Monitoring Resolved 2025-07-01
MR Monitoring Resolved 2024-09-29
MR Monitoring Resolved 2024-09-29
MR Monitoring Resolved 2024-09-29
MR Monitoring Resolved 2016-12-30
MR Monitoring Resolved 2016-12-30
Other Monitoring Resolved 2016-07-01
Other Monitoring Resolved 2016-07-01

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the single worst sample on record — over 100% is worth reading, but is not by itself a violation. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
275 µg/L 21%
of the EPA limit 1300 µg/L
50/63 SYR4 2013–2019
Nitrate
500 µg/L 5%
of the EPA limit 10000 µg/L
48/48 SYR4 2012–2019
Lead
20.2 µg/L 135%
of the EPA limit, in the worst sample — 15 µg/L
24/63 SYR4 2013–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
18/18 LCR 2024
Nitrate-Nitrite
500 µg/L 5%
of the EPA limit 10000 µg/L
12/12 SYR4 2012–2019
Barium
151 µg/L 7.6%
of the EPA limit 2000 µg/L
6/6 SYR4 2016–2019
Fluoride
210 µg/L 5.3%
of the EPA limit 4000 µg/L
6/6 SYR4 2014–2017
Combined Radium (-226 And -228)
3 pCi/L 60%
of the EPA limit 5 pCi/L
3/3 SYR4 2016
Dibromochloromethane
1.4 µg/L
No EPA limit set
3/28 SYR4 2013–2019
Xylenes, Total
0.7000 µg/L 0%
of the EPA limit 10000 µg/L
3/19 SYR4 2015–2019
Arsenic
2.5 µg/L 25%
of the EPA limit 10 µg/L
2/6 SYR4 2016–2019
Bromodichloromethane
1.1 µg/L
No EPA limit set
2/28 SYR4 2013–2019
TTHM
2.3 µg/L 2.9%
of the EPA limit 80 µg/L
2/9 SYR4 2013–2019
Bromoform
1.1 µg/L
No EPA limit set
1/28 SYR4 2013–2019
Gross Alpha, Excl. Radon And U
3 pCi/L 20%
of the EPA limit 15 pCi/L
1/3 SYR4 2016
Selenium
3.1 µg/L 6.2%
of the EPA limit 50 µg/L
1/6 SYR4 2016–2019
Lithium
13.5 µg/L
No EPA limit set
1/6 UCMR-5 2023
92 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalAsbestosAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChloroformChromiumCombined UraniumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDibromoacetic AcidDichloroacetic AcidDinosebEthylene DibromideEndrinEthylbenzeneGross Beta Particle ActivityHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidNetfosaaNfdhaNmefosaaNitriteOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Haloacetic Acids (HAA5)ToxapheneTrichloroacetic AcidTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
BILSKI, CAROLYN
Phone
979-256-7028
Email
cbilski@ci.sealy.tx.us

Frequently asked questions about City of Sealy

Is City of Sealy tap water safe to drink?

EPA monitoring detected 17 contaminants in City of Sealy's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in City of Sealy's water?

EPA monitoring detected Copper, Nitrate, Lead, Lead, Nitrate-Nitrite, and others. The full list with the level and data source for each is above.

How many people does City of Sealy serve?

City of Sealy reports serving 6,839 people in Texas, per its EPA record.

Has City of Sealy had any water quality violations?

The EPA has 12 violations on file for City of Sealy, of which 1 is health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.