← South Carolina

Tap water quality report

Kingstree Town of (sc4510002)

EPA monitoring tested this supplier for 109 contaminants and detected 21. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

109
contaminants tested
21
detected
6,009
people served
5
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Williamsburg

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

5
health-based violations
68
violations on file
8
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2011-01-01 → 2011-01-31
MCL Health-based Resolved 2011-01-01 → 2011-01-31
MCL Health-based Resolved 2011-01-01 → 2011-01-31
MCL Health-based Resolved 2011-01-01 → 2011-01-31
MCL Health-based Archived 1995-07-01 → 1995-07-31
MR Monitoring Resolved 2024-04-02
MR Monitoring Resolved 2024-04-02
MR Monitoring Resolved 2024-04-02
MR Monitoring Resolved 2024-04-02
MR Monitoring Resolved 2024-04-02

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the single worst sample on record — over 100% is worth reading, but is not by itself a violation. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
140 µg/L 11%
of the EPA limit 1300 µg/L
51/60 SYR4 2012–2018
Fluoride
2400 µg/L 60%
of the EPA limit 4000 µg/L
24/24 SYR4 2012–2019
Lead
11 µg/L 73%
of the EPA limit 15 µg/L
21/60 SYR4 2012–2018
Lead
0.0029 mg/L 19%
of the EPA limit 0.0150 mg/L
17/17 LCR 2024
Nitrate
2400 µg/L 24%
of the EPA limit 10000 µg/L
8/64 SYR4 2012–2019
Bromodichloromethane
12.33 µg/L
No EPA limit set
7/7 SYR4 2013–2019
Bromoform
21.58 µg/L
No EPA limit set
7/7 SYR4 2013–2019
Dibromochloromethane
11.41 µg/L
No EPA limit set
7/7 SYR4 2013–2019
TTHM
36.39 µg/L 45%
of the EPA limit 80 µg/L
7/7 SYR4 2013–2019
Chloroform
14.1004 µg/L
No EPA limit set
6/7 SYR4 2013–2019
Dibromoacetic Acid
3.74 µg/L
No EPA limit set
6/7 SYR4 2013–2019
Dichloroacetic Acid
5.61 µg/L
No EPA limit set
6/7 SYR4 2013–2019
Total Haloacetic Acids (HAA5)
26.84 µg/L 45%
of the EPA limit 60 µg/L
6/7 SYR4 2013–2019
Trichloroacetic Acid
5.84 µg/L
No EPA limit set
6/7 SYR4 2013–2019
Monobromoacetic Acid
13.62 µg/L
No EPA limit set
5/7 SYR4 2013–2019
Gross Alpha, Excl. Radon And U
1.14 pCi/L 7.6%
of the EPA limit 15 pCi/L
3/8 SYR4 2012–2019
Antimony, Total
0.1100 µg/L 1.8%
of the EPA limit 6 µg/L
1/12 SYR4 2013–2019
Cadmium
0.1400 µg/L 2.8%
of the EPA limit 5 µg/L
1/12 SYR4 2013–2019
Combined Radium (-226 And -228)
0.6270 pCi/L 13%
of the EPA limit 5 pCi/L
1/8 SYR4 2012–2019
Di(2-ethylhexyl) Phthalate
1.4 µg/L 23%
of the EPA limit 6 µg/L
1/12 SYR4 2013–2019
Nitrate-Nitrite
2400 µg/L 24%
of the EPA limit 10000 µg/L
1/4 SYR4 2013
88 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaArsenicAtrazineBhc-GammaBariumBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCarbofuranCarbon TetrachlorideChlordaneChromiumCombined UraniumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDinosebDiquatEthylene DibromideEndrinEthylbenzeneGlyphosateGross Beta Particle ActivityHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonochloroacetic AcidNetfosaaNfdhaNmefosaaNitriteOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
COKER, KIPPTON
Phone
843-355-7484
Email
kcoker@kingstree.org; CTISDALE@KINGSTREE.ORG; THUELL@KINGSTREE.ORG

Frequently asked questions about Kingstree Town of (sc4510002)

Is Kingstree Town of (sc4510002) tap water safe to drink?

EPA monitoring detected 21 contaminants in Kingstree Town of (sc4510002)'s water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Kingstree Town of (sc4510002)'s water?

EPA monitoring detected Copper, Fluoride, Lead, Lead, Nitrate, and others. The full list with the level and data source for each is above.

How many people does Kingstree Town of (sc4510002) serve?

Kingstree Town of (sc4510002) reports serving 6,009 people in South Carolina, per its EPA record.

Has Kingstree Town of (sc4510002) had any water quality violations?

The EPA has 68 violations on file for Kingstree Town of (sc4510002), of which 5 are health-based (a contaminant limit or required treatment was breached) and 8 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.