← South Carolina

Tap water quality report

Bgwc Peachtree Acres (3250045)

EPA monitoring tested this supplier for 14 contaminants and detected 14. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

14
contaminants tested
14
detected
124
people served
14
health-based violations
Water source
SWP
Ownership
Private
Counties served
Lexington

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

14
health-based violations
22
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2016-10-01 → 2016-12-31
MCL Health-based Resolved 2016-10-01 → 2016-12-31
MCL Health-based Resolved 2016-10-01 → 2016-12-31
MCL Health-based Resolved 2016-10-01 → 2016-12-31
MCL Health-based Resolved 2016-10-01 → 2016-12-31
MCL Health-based Resolved 2016-10-01 → 2016-12-31
MCL Health-based Resolved 2016-10-01 → 2016-12-31
MCL Health-based Resolved 2016-10-01 → 2016-12-31
MCL Health-based Resolved 2016-10-01 → 2016-12-31
MCL Health-based Resolved 2016-10-01 → 2016-12-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
1632 µg/L 126%
of the EPA limit, at the 95th percentile of samples — 1300 µg/L
worst single sample: 5920 µg/L
35/41 SYR4 2012–2018
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
14/14 LCR 2024
TTHM
27.8551 µg/L 35%
of the EPA limit 80 µg/L
worst single sample: 29.2 µg/L
8/8 SYR4 2014–2019
Total Haloacetic Acids (HAA5)
35.0065 µg/L 58%
of the EPA limit 60 µg/L
worst single sample: 35.08 µg/L
8/8 SYR4 2014–2019
Bromodichloromethane
7.069 µg/L
No EPA limit set
worst single sample: 7.48 µg/L
7/8 SYR4 2014–2019
Lead
7.7 µg/L 51%
of the EPA limit 15 µg/L
worst single sample: 8 µg/L
7/41 SYR4 2012–2018
Chloroform
19.9454 µg/L
No EPA limit set
worst single sample: 20.43 µg/L
6/8 SYR4 2014–2019
Dibromochloromethane
5.485 µg/L
No EPA limit set
worst single sample: 6.45 µg/L
6/8 SYR4 2014–2019
Trichloroacetic Acid
10.565 µg/L
No EPA limit set
worst single sample: 11.15 µg/L
6/8 SYR4 2014–2019
Dichloroacetic Acid
25.534 µg/L
No EPA limit set
worst single sample: 26.27 µg/L
5/8 SYR4 2014–2019
Bromoform
2.9575 µg/L
No EPA limit set
worst single sample: 3.06 µg/L
2/8 SYR4 2014–2019
Dibromoacetic Acid
2.625 µg/L
No EPA limit set
worst single sample: 2.69 µg/L
2/8 SYR4 2014–2019
Monobromoacetic Acid
2.959 µg/L
No EPA limit set
worst single sample: 3.04 µg/L
2/8 SYR4 2014–2019
Monochloroacetic Acid
3.726 µg/L
No EPA limit set
worst single sample: 3.77 µg/L
2/8 SYR4 2014–2019

Utility contact

Contact
BLUE GRANITE WATER COMPANY
Phone
864-483-4268
Email
ADAM.ROBINSON@NEXUSWG.COM

Frequently asked questions about Bgwc Peachtree Acres (3250045)

Is Bgwc Peachtree Acres (3250045) tap water safe to drink?

EPA monitoring detected 14 contaminants in Bgwc Peachtree Acres (3250045)'s water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Bgwc Peachtree Acres (3250045)'s water?

EPA monitoring detected Copper, Lead, TTHM, Total Haloacetic Acids (HAA5), Bromodichloromethane, and others. The full list with the level and data source for each is above.

How many people does Bgwc Peachtree Acres (3250045) serve?

Bgwc Peachtree Acres (3250045) reports serving 124 people in South Carolina, per its EPA record.

Has Bgwc Peachtree Acres (3250045) had any water quality violations?

The EPA has 22 violations on file for Bgwc Peachtree Acres (3250045), of which 14 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.