← South Carolina

Tap water quality report

Bgwc Idlewood (sc3250017)

EPA monitoring tested this supplier for 14 contaminants and detected 11. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

14
contaminants tested
11
detected
134
people served
19
health-based violations
Water source
SWP
Ownership
Private
Counties served
Lexington

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

19
health-based violations
50
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2000-10-01 → 2000-12-31
MCL Health-based Resolved 2000-10-01 → 2000-12-31
MCL Health-based Resolved 2000-10-01 → 2000-12-31
MCL Health-based Resolved 2000-10-01 → 2000-12-31
MCL Health-based Resolved 2000-10-01 → 2000-12-31
MCL Health-based Resolved 2000-10-01 → 2000-12-31
MCL Health-based Resolved 2000-07-01 → 2000-09-30
MCL Health-based Resolved 2000-07-01 → 2000-09-30
MCL Health-based Resolved 2000-07-01 → 2000-09-30
MCL Health-based Resolved 2000-07-01 → 2000-09-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
77 µg/L 5.9%
of the EPA limit 1300 µg/L
worst single sample: 86 µg/L
25/25 SYR4 2013–2018
Lead
0.0060 mg/L 40%
of the EPA limit 0.0150 mg/L
16/16 LCR 2025
Bromodichloromethane
13.906 µg/L
No EPA limit set
worst single sample: 15.85 µg/L
7/8 SYR4 2014–2019
Chloroform
65.851 µg/L
No EPA limit set
worst single sample: 78.7 µg/L
7/8 SYR4 2014–2019
TTHM
81.768 µg/L 102%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 96.9 µg/L
7/8 SYR4 2014–2019
Dibromochloromethane
2.19774 µg/L
No EPA limit set
worst single sample: 2.3 µg/L
5/8 SYR4 2014–2019
Lead
5.6 µg/L 37%
of the EPA limit 15 µg/L
worst single sample: 6 µg/L
5/25 SYR4 2013–2018
Dichloroacetic Acid
8.487 µg/L
No EPA limit set
worst single sample: 8.53 µg/L
2/8 SYR4 2014–2019
Monobromoacetic Acid
1.286 µg/L
No EPA limit set
worst single sample: 1.3 µg/L
2/8 SYR4 2014–2019
Total Haloacetic Acids (HAA5)
38.165 µg/L 64%
of the EPA limit 60 µg/L
worst single sample: 39.4 µg/L
2/8 SYR4 2014–2019
Trichloroacetic Acid
28.596 µg/L
No EPA limit set
worst single sample: 29.8 µg/L
2/8 SYR4 2014–2019
3 contaminants tested, none detected
BromoformDibromoacetic AcidMonochloroacetic Acid

Utility contact

Contact
BLUE GRANITE WATER COMPANY
Phone
864-483-4268
Email
ADAM.ROBINSON@NEXUSWG.COM

Frequently asked questions about Bgwc Idlewood (sc3250017)

Is Bgwc Idlewood (sc3250017) tap water safe to drink?

EPA monitoring detected 11 contaminants in Bgwc Idlewood (sc3250017)'s water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Bgwc Idlewood (sc3250017)'s water?

EPA monitoring detected Copper, Lead, Bromodichloromethane, Chloroform, TTHM, and others. The full list with the level and data source for each is above.

How many people does Bgwc Idlewood (sc3250017) serve?

Bgwc Idlewood (sc3250017) reports serving 134 people in South Carolina, per its EPA record.

Has Bgwc Idlewood (sc3250017) had any water quality violations?

The EPA has 50 violations on file for Bgwc Idlewood (sc3250017), of which 19 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.