Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2003-11-01 → 2003-11-30 |
| MCL | Health-based | Resolved | 2003-07-01 → 2003-07-31 |
| MCL | Health-based | Resolved | 2003-07-01 → 2003-07-31 |
| MCL | Health-based | Resolved | 2003-01-01 → 2003-03-31 |
| MCL | Health-based | Resolved | 2003-01-01 → 2003-03-31 |
| MCL | Health-based | Resolved | 2003-01-01 → 2003-03-31 |
| MCL | Health-based | Archived | 2002-10-01 → 2002-12-31 |
| MCL | Health-based | Archived | 2002-10-01 → 2002-12-31 |
| MCL | Health-based | Archived | 2002-07-01 → 2002-09-30 |
| MCL | Health-based | Archived | 2002-07-01 → 2002-09-30 |
PFAS detected
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromodichloromethane | 110 µg/L No EPA limit set | 248/248 | SYR4 | 2012–2019 |
| TTHM | 73.9 µg/L 92% of the EPA limit 80 µg/L | 248/248 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 50.8 µg/L 85% of the EPA limit 60 µg/L | 248/248 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 17.86 µg/L No EPA limit set | 247/248 | SYR4 | 2012–2019 |
| Dibromochloromethane | 17.1 µg/L No EPA limit set | 245/248 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 27.2 µg/L No EPA limit set | 245/248 | SYR4 | 2012–2019 |
| Chloroform | 44.4 µg/L No EPA limit set | 242/248 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 4.9 µg/L No EPA limit set | 128/248 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 11.61 µg/L No EPA limit set | 113/248 | SYR4 | 2012–2019 |
| Copper | 820 µg/L 63% of the EPA limit 1300 µg/L | 53/61 | SYR4 | 2014–2017 |
| Bromoform | 25.7 µg/L No EPA limit set | 44/248 | SYR4 | 2012–2019 |
| Lead | 0.0022 mg/L 15% of the EPA limit 0.0150 mg/L | 20/20 | LCR | 2023 |
| Nitrate | 880 µg/L 8.8% of the EPA limit 10000 µg/L | 16/16 | SYR4 | 2012–2019 |
| Lead | 5.2 µg/L 35% of the EPA limit 15 µg/L | 15/61 | SYR4 | 2014–2017 |
| Fluoride | 780 µg/L 20% of the EPA limit 4000 µg/L | 7/8 | SYR4 | 2012–2019 |
| Chlorobenzene | 0.7000 µg/L 0.7% of the EPA limit 100 µg/L | 1/18 | SYR4 | 2012–2019 |
85 contaminants tested, none detected
Utility contact
Frequently asked questions about Camden City of (sc2810001)
Is Camden City of (sc2810001) tap water safe to drink?
EPA monitoring detected 20 contaminants in Camden City of (sc2810001)'s water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Camden City of (sc2810001)'s water?
EPA monitoring detected Bromodichloromethane, TTHM, Total Haloacetic Acids (HAA5), Trichloroacetic Acid, Dibromochloromethane, and others. The full list with the level and data source for each is above.
How many people does Camden City of (sc2810001) serve?
Camden City of (sc2810001) reports serving 19,076 people in South Carolina, per its EPA record.
Has Camden City of (sc2810001) had any water quality violations?
The EPA has 32 violations on file for Camden City of (sc2810001), of which 19 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.