← Pennsylvania

Tap water quality report

Hawk Valley Village

EPA monitoring tested this supplier for 79 contaminants and detected 18. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

79
contaminants tested
18
detected
250
people served
7
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Lancaster

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

7
health-based violations
200
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 1988-06-24 → 1991-06-23
MCL Health-based Resolved 1988-06-24 → 1991-06-23
MCL Health-based Resolved 1988-06-24 → 1991-06-23
MCL Health-based Resolved 1988-06-24 → 1991-06-23
MCL Health-based Resolved 1988-06-24 → 1991-06-23
MCL Health-based Resolved 1988-06-24 → 1991-06-23
MCL Health-based Resolved 1988-06-24 → 1991-06-23
Other Monitoring Resolved 2025-10-01
Other Monitoring Resolved 2025-10-01
MR Monitoring Resolved 2024-10-01 → 2024-10-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the single worst sample on record — over 100% is worth reading, but is not by itself a violation. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
9620 µg/L 96%
of the EPA limit 10000 µg/L
64/64 SYR4 2012–2019
Copper
1970 µg/L 152%
of the EPA limit, in the worst sample — 1300 µg/L
45/70 SYR4 2012–2019
Lead
22 µg/L 147%
of the EPA limit, in the worst sample — 15 µg/L
7/70 SYR4 2012–2019
Xylenes, Total
5.3 µg/L 0.1%
of the EPA limit 10000 µg/L
5/9 SYR4 2012–2019
Dibromochloromethane
4.8 µg/L
No EPA limit set
4/4 SYR4 2013–2018
TTHM
19 µg/L 24%
of the EPA limit 80 µg/L
4/4 SYR4 2013–2018
Bromodichloromethane
5.5 µg/L
No EPA limit set
3/4 SYR4 2013–2018
Chloroform
6.1 µg/L
No EPA limit set
3/4 SYR4 2013–2018
Lead
0.0049 mg/L 33%
of the EPA limit 0.0150 mg/L
3/3 LCR 1996
Total Haloacetic Acids (HAA5)
4.28 µg/L 7.1%
of the EPA limit 60 µg/L
3/4 SYR4 2013–2018
Arsenic
2 µg/L 20%
of the EPA limit 10 µg/L
2/3 SYR4 2012–2018
Barium
16 µg/L 0.8%
of the EPA limit 2000 µg/L
2/3 SYR4 2012–2018
Bromoform
2.6 µg/L
No EPA limit set
2/4 SYR4 2013–2018
Chromium
2 µg/L 2%
of the EPA limit 100 µg/L
2/3 SYR4 2012–2018
Ethylbenzene
0.8000 µg/L 0.1%
of the EPA limit 700 µg/L
2/9 SYR4 2012–2019
Dibromoacetic Acid
1.51 µg/L
No EPA limit set
1/1 SYR4 2018
Dichloroacetic Acid
1.18 µg/L
No EPA limit set
1/1 SYR4 2018
Trichloroacetic Acid
1.59 µg/L
No EPA limit set
1/1 SYR4 2018
61 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,3,7,8-TCDD2,4,5-TP2,4-DAntimony, TotalAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneCombined UraniumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndothallEndrinFluorideGlyphosateHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidNitriteOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
LARRY MILLER
Phone
717-445-4033

Frequently asked questions about Hawk Valley Village

Is Hawk Valley Village tap water safe to drink?

EPA monitoring detected 18 contaminants in Hawk Valley Village's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Hawk Valley Village's water?

EPA monitoring detected Nitrate, Copper, Lead, Xylenes, Total, Dibromochloromethane, and others. The full list with the level and data source for each is above.

How many people does Hawk Valley Village serve?

Hawk Valley Village reports serving 250 people in Pennsylvania, per its EPA record.

Has Hawk Valley Village had any water quality violations?

The EPA has 200 violations on file for Hawk Valley Village, of which 7 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.