Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2014-07-01 → 2014-07-31 |
| MCL | Health-based | Resolved | 2014-07-01 → 2014-07-31 |
| MCL | Health-based | Resolved | 2014-07-01 → 2014-07-31 |
| TT | Health-based | Resolved | 2012-04-01 → 2012-06-30 |
| TT | Health-based | Resolved | 2012-04-01 → 2012-06-30 |
| TT | Health-based | Resolved | 2012-04-01 → 2012-06-30 |
| TT | Health-based | Resolved | 2003-11-01 → 2003-11-30 |
| RPT | Monitoring | Resolved | 2025-05-11 |
| RPT | Monitoring | Resolved | 2025-05-11 |
| MR | Monitoring | Resolved | 2024-03-01 → 2024-03-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromodichloromethane | 8.39 µg/L No EPA limit set | 122/128 | SYR4 | 2012–2019 |
| Chloroform | 91.6 µg/L No EPA limit set | 122/128 | SYR4 | 2012–2019 |
| TTHM | 98.9 µg/L 124% of the EPA limit, in the worst sample — 80 µg/L | 122/128 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 66 µg/L 110% of the EPA limit, in the worst sample — 60 µg/L | 118/128 | SYR4 | 2012–2019 |
| Copper | 620 µg/L 48% of the EPA limit 1300 µg/L | 94/94 | SYR4 | 2013–2019 |
| Lead | 160 µg/L 1067% of the EPA limit, in the worst sample — 15 µg/L | 65/97 | SYR4 | 2013–2019 |
| Dichloroacetic Acid | 25 µg/L No EPA limit set | 20/20 | SYR4 | 2018–2019 |
| Trichloroacetic Acid | 52 µg/L No EPA limit set | 20/20 | SYR4 | 2018–2019 |
| Lead | 0.0060 mg/L 40% of the EPA limit 0.0150 mg/L | 16/16 | LCR | 2025 |
| Nitrate | 1220 µg/L 12% of the EPA limit 10000 µg/L | 16/54 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 1.7 µg/L No EPA limit set | 10/20 | SYR4 | 2018–2019 |
| Barium | 220 µg/L 11% of the EPA limit 2000 µg/L | 8/12 | SYR4 | 2012–2019 |
| Dibromochloromethane | 0.9800 µg/L No EPA limit set | 8/128 | SYR4 | 2012–2019 |
| Fluoride | 959 µg/L 24% of the EPA limit 4000 µg/L | 8/12 | SYR4 | 2012–2019 |
| Nitrite | 860 µg/L 86% of the EPA limit 1000 µg/L | 2/27 | SYR4 | 2012–2019 |
| Di(2-ethylhexyl) Phthalate | 0.6320 µg/L 11% of the EPA limit 6 µg/L | 1/15 | SYR4 | 2012–2019 |
94 contaminants tested, none detected
Utility contact
Frequently asked questions about Boro of Waynesboro
Is Boro of Waynesboro tap water safe to drink?
EPA monitoring detected 16 contaminants in Boro of Waynesboro's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Boro of Waynesboro's water?
EPA monitoring detected Bromodichloromethane, Chloroform, TTHM, Total Haloacetic Acids (HAA5), Copper, and others. The full list with the level and data source for each is above.
How many people does Boro of Waynesboro serve?
Boro of Waynesboro reports serving 13,200 people in Pennsylvania, per its EPA record.
Has Boro of Waynesboro had any water quality violations?
The EPA has 501 violations on file for Boro of Waynesboro, of which 7 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.