← Pennsylvania

Tap water quality report

Eastern Cumberland Water Sys

EPA monitoring tested this supplier for 79 contaminants and detected 17. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

79
contaminants tested
17
detected
150
people served
2
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Adams

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

2
health-based violations
77
violations on file
0
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2012-12-01 → 2012-12-31
TT Health-based Resolved 2012-12-01 → 2012-12-31
MR Monitoring Archived 2025-10-01 → 2025-10-31
MR Monitoring Archived 2025-10-01 → 2025-10-31
MR Monitoring Resolved 2022-07-01 → 2022-09-30
MR Monitoring Resolved 2022-07-01 → 2022-09-30
MR Monitoring Resolved 2022-07-01 → 2022-09-30
MR Monitoring Resolved 2022-07-01 → 2022-09-30
MR Monitoring Resolved 2022-07-01 → 2022-09-30
MR Monitoring Resolved 2022-07-01 → 2022-09-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the single worst sample on record — over 100% is worth reading, but is not by itself a violation. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
1400 µg/L 14%
of the EPA limit 10000 µg/L
16/16 SYR4 2012–2019
Copper
250 µg/L 19%
of the EPA limit 1300 µg/L
14/16 SYR4 2013–2019
Bromodichloromethane
16.3 µg/L
No EPA limit set
8/8 SYR4 2013–2019
Chloroform
51.6 µg/L
No EPA limit set
8/8 SYR4 2013–2019
Dibromochloromethane
5.3 µg/L
No EPA limit set
8/8 SYR4 2013–2019
TTHM
74.8 µg/L 94%
of the EPA limit 80 µg/L
7/7 SYR4 2013–2019
Bromoform
1.6 µg/L
No EPA limit set
6/8 SYR4 2013–2019
Total Haloacetic Acids (HAA5)
10.7 µg/L 18%
of the EPA limit 60 µg/L
6/7 SYR4 2013–2019
Lead
6 µg/L 40%
of the EPA limit 15 µg/L
5/16 SYR4 2013–2019
Arsenic
5 µg/L 50%
of the EPA limit 10 µg/L
3/3 SYR4 2012–2018
Barium
185 µg/L 9.3%
of the EPA limit 2000 µg/L
2/3 SYR4 2012–2018
Combined Uranium
2.831 µg/L 9.4%
of the EPA limit 30 µg/L
2/2 SYR4 2013–2019
Dichloroacetic Acid
3.2 µg/L
No EPA limit set
2/2 SYR4 2018–2019
Trichloroacetic Acid
2.2 µg/L
No EPA limit set
2/2 SYR4 2018–2019
Chromium
2.1 µg/L 2.1%
of the EPA limit 100 µg/L
1/3 SYR4 2012–2018
Dibromoacetic Acid
1.1 µg/L
No EPA limit set
1/2 SYR4 2018–2019
Lead
0.0063 mg/L 42%
of the EPA limit 0.0150 mg/L
1/1 LCR 1994
62 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,3,7,8-TCDD2,4,5-TP2,4-DAntimony, TotalAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneFluorideGlyphosateHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidNitriteOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
DOUG CRAWSHAW
Phone
717-718-2974

Frequently asked questions about Eastern Cumberland Water Sys

Is Eastern Cumberland Water Sys tap water safe to drink?

EPA monitoring detected 17 contaminants in Eastern Cumberland Water Sys's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Eastern Cumberland Water Sys's water?

EPA monitoring detected Nitrate, Copper, Bromodichloromethane, Chloroform, Dibromochloromethane, and others. The full list with the level and data source for each is above.

How many people does Eastern Cumberland Water Sys serve?

Eastern Cumberland Water Sys reports serving 150 people in Pennsylvania, per its EPA record.

Has Eastern Cumberland Water Sys had any water quality violations?

The EPA has 77 violations on file for Eastern Cumberland Water Sys, of which 2 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.