Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2021-07-30 |
| TT | Health-based | Resolved | 2021-07-30 |
| MCL | Health-based | Resolved | 2021-06-01 → 2021-06-30 |
| MCL | Health-based | Resolved | 2021-06-01 → 2021-06-30 |
| MCL | Health-based | Resolved | 2021-06-01 → 2021-06-30 |
| MCL | Health-based | Resolved | 2021-06-01 → 2021-06-30 |
| MCL | Health-based | Resolved | 2007-12-01 → 2007-12-31 |
| MCL | Health-based | Resolved | 2007-12-01 → 2007-12-31 |
| MR | Monitoring | Archived | 2025-11-01 → 2025-11-30 |
| MR | Monitoring | Archived | 2025-11-01 → 2025-11-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 595.35 µg/L 46% of the EPA limit 1300 µg/L
worst single sample: 688 µg/L | 80/80 | SYR4 | 2013–2019 |
| Bromodichloromethane | 10.17 µg/L No EPA limit set
worst single sample: 11.8 µg/L | 64/64 | SYR4 | 2012–2019 |
| TTHM | 62.95 µg/L 79% of the EPA limit 80 µg/L
worst single sample: 75.9 µg/L | 64/64 | SYR4 | 2012–2019 |
| Chloroform | 51 µg/L No EPA limit set
worst single sample: 62.4 µg/L | 63/64 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 42.17 µg/L 70% of the EPA limit 60 µg/L
worst single sample: 50.5 µg/L | 63/64 | SYR4 | 2012–2019 |
| Dibromochloromethane | 4.01 µg/L No EPA limit set
worst single sample: 6.12 µg/L | 56/64 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 22.3 µg/L No EPA limit set
worst single sample: 23 µg/L | 15/16 | SYR4 | 2015–2019 |
| Trichloroacetic Acid | 23.96 µg/L No EPA limit set
worst single sample: 27.6 µg/L | 15/16 | SYR4 | 2015–2019 |
| Lead | 0.0018 mg/L 12% of the EPA limit 0.0150 mg/L | 11/11 | LCR | 2025 |
| Bromoform | 2.553 µg/L No EPA limit set
worst single sample: 2.79 µg/L | 7/64 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 20.5 µg/L No EPA limit set
worst single sample: 21 µg/L | 3/16 | SYR4 | 2015–2019 |
| Barium | 34.185 µg/L 1.7% of the EPA limit 2000 µg/L
worst single sample: 34.3 µg/L | 2/3 | SYR4 | 2012–2018 |
| Nitrate | 1670 µg/L 17% of the EPA limit 10000 µg/L | 2/16 | SYR4 | 2012–2019 |
| Lithium | 10.5 µg/L No EPA limit set | 2/8 | UCMR-5 | 2023 |
| Dalapon | 1.4 µg/L 0.7% of the EPA limit 200 µg/L | 1/11 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 2 µg/L No EPA limit set | 1/16 | SYR4 | 2015–2019 |
| Fluoride | 649 µg/L 16% of the EPA limit 4000 µg/L | 1/3 | SYR4 | 2012–2018 |
| Monobromoacetic Acid | 1 µg/L No EPA limit set | 1/16 | SYR4 | 2015–2019 |
| Picloram | 0.1200 µg/L 0% of the EPA limit 500 µg/L | 1/11 | SYR4 | 2012–2019 |
91 contaminants tested, none detected
Utility contact
Frequently asked questions about Mountain Water Assn
Is Mountain Water Assn tap water safe to drink?
EPA monitoring detected 19 contaminants in Mountain Water Assn's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Mountain Water Assn's water?
EPA monitoring detected Copper, Bromodichloromethane, TTHM, Chloroform, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.
How many people does Mountain Water Assn serve?
Mountain Water Assn reports serving 3,856 people in Pennsylvania, per its EPA record.
Has Mountain Water Assn had any water quality violations?
The EPA has 276 violations on file for Mountain Water Assn, of which 8 are health-based (a contaminant limit or required treatment was breached) and 2 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.