← Pennsylvania

Tap water quality report

Rote Mutual Water Association

EPA monitoring tested this supplier for 50 contaminants and detected 12. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

50
contaminants tested
12
detected
481
people served
33
health-based violations
Water source
Ground water under surface influence
Ownership
Private
Counties served
Clinton

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

33
health-based violations
215
violations on file
0
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2025-03-01 → 2025-03-31
TT Health-based Resolved 2025-03-01 → 2025-03-31
TT Health-based Resolved 2025-03-01 → 2025-03-31
TT Health-based Resolved 2025-03-01 → 2025-03-31
TT Health-based Resolved 2024-01-01 → 2024-01-31
TT Health-based Resolved 2024-01-01 → 2024-01-31
TT Health-based Resolved 2024-01-01 → 2024-01-31
TT Health-based Resolved 2024-01-01 → 2024-01-31
TT Health-based Resolved 2024-01-01 → 2024-01-31
TT Health-based Resolved 2021-03-01 → 2021-03-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the single worst sample on record — over 100% is worth reading, but is not by itself a violation. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
524 µg/L 40%
of the EPA limit 1300 µg/L
36/37 SYR4 2013–2019
Bromodichloromethane
4.3 µg/L
No EPA limit set
8/8 SYR4 2012–2019
Chloroform
17.9 µg/L
No EPA limit set
8/8 SYR4 2012–2019
TTHM
22.1 µg/L 28%
of the EPA limit 80 µg/L
8/8 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
20.3 µg/L 34%
of the EPA limit 60 µg/L
8/8 SYR4 2012–2019
Dibromochloromethane
2.14 µg/L
No EPA limit set
6/8 SYR4 2012–2019
Dichloroacetic Acid
12.6 µg/L
No EPA limit set
4/4 SYR4 2015–2019
Lead
0.9960 µg/L 6.6%
of the EPA limit 15 µg/L
4/27 SYR4 2013–2019
Nitrate
120 µg/L 1.2%
of the EPA limit 10000 µg/L
4/16 SYR4 2012–2019
Trichloroacetic Acid
7.78 µg/L
No EPA limit set
4/4 SYR4 2015–2019
Lead
0.0120 mg/L 80%
of the EPA limit 0.0150 mg/L
2/2 LCR 1996
Barium
15.2 µg/L 0.8%
of the EPA limit 2000 µg/L
1/2 SYR4 2012
38 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-DichloropropaneAntimony, TotalArsenicBenzeneBeryllium, TotalBromoformChlorobenzeneCyanideCadmiumCarbon TetrachlorideChromiumCombined UraniumDichloromethaneDibromoacetic AcidEthylbenzeneFluorideGlyphosateMercuryMonobromoacetic AcidMonochloroacetic AcidNitriteSeleniumStyreneTetrachloroethyleneThallium, TotalTolueneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
ROB REEM, PRE
Phone
570-660-5627

Frequently asked questions about Rote Mutual Water Association

Is Rote Mutual Water Association tap water safe to drink?

EPA monitoring detected 12 contaminants in Rote Mutual Water Association's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Rote Mutual Water Association's water?

EPA monitoring detected Copper, Bromodichloromethane, Chloroform, TTHM, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.

How many people does Rote Mutual Water Association serve?

Rote Mutual Water Association reports serving 481 people in Pennsylvania, per its EPA record.

Has Rote Mutual Water Association had any water quality violations?

The EPA has 215 violations on file for Rote Mutual Water Association, of which 33 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.