← Pennsylvania

Tap water quality report

Aqua Pa Midway

EPA monitoring tested this supplier for 78 contaminants and detected 22. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

78
contaminants tested
22
detected
2,450
people served
4
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Luzerne

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

4
health-based violations
278
violations on file
0
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2013-03-01 → 2013-03-31
TT Health-based Resolved 2013-03-01 → 2013-03-31
TT Health-based Resolved 2013-03-01 → 2013-03-31
TT Health-based Resolved 2013-03-01 → 2013-03-31
MR Monitoring Resolved 2024-03-01 → 2024-03-31
MR Monitoring Resolved 2024-03-01 → 2024-03-31
MR Monitoring Resolved 2020-12-01 → 2020-12-31
MR Monitoring Resolved 2020-12-01 → 2020-12-31
MR Monitoring Resolved 2014-10-01 → 2014-12-31
MR Monitoring Resolved 2014-10-01 → 2014-12-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
276.5 µg/L 21%
of the EPA limit 1300 µg/L
worst single sample: 580 µg/L
28/32 SYR4 2013–2019
Nitrate
1500 µg/L 15%
of the EPA limit 10000 µg/L
26/54 SYR4 2012–2019
Barium
197 µg/L 9.9%
of the EPA limit 2000 µg/L
worst single sample: 202 µg/L
11/11 SYR4 2012–2019
Chromium
3.7 µg/L 3.7%
of the EPA limit 100 µg/L
worst single sample: 4.1 µg/L
11/11 SYR4 2012–2019
TTHM
21.785 µg/L 27%
of the EPA limit 80 µg/L
worst single sample: 22.1 µg/L
10/10 SYR4 2012–2019
Lead
7.095 µg/L 47%
of the EPA limit 15 µg/L
worst single sample: 7.2 µg/L
8/32 SYR4 2013–2019
Arsenic
3.24 µg/L 32%
of the EPA limit 10 µg/L
worst single sample: 3.6 µg/L
7/11 SYR4 2012–2019
Chloroform
7.1 µg/L
No EPA limit set
6/6 SYR4 2017–2019
Total Haloacetic Acids (HAA5)
6.925 µg/L 12%
of the EPA limit 60 µg/L
worst single sample: 7.4 µg/L
6/10 SYR4 2012–2019
Bromodichloromethane
6.26 µg/L
No EPA limit set
worst single sample: 6.3 µg/L
3/3 SYR4 2017–2019
Bromoform
3.71 µg/L
No EPA limit set
worst single sample: 4 µg/L
3/3 SYR4 2017–2019
Dibromochloromethane
6.86 µg/L
No EPA limit set
worst single sample: 7.2 µg/L
3/3 SYR4 2017–2019
Dichloroacetic Acid
3.94 µg/L
No EPA limit set
worst single sample: 4.1 µg/L
3/3 SYR4 2017–2019
Lead
0.0080 mg/L 53%
of the EPA limit 0.0150 mg/L
3/3 LCR 1996
Xylenes, Total
2.12 µg/L 0%
of the EPA limit 10000 µg/L
worst single sample: 2.2 µg/L
3/12 SYR4 2014–2019
Combined Uranium
2.29609 µg/L 7.7%
of the EPA limit 30 µg/L
2/4 SYR4 2012–2015
Dibromoacetic Acid
1.59 µg/L
No EPA limit set
worst single sample: 1.6 µg/L
2/3 SYR4 2017–2019
Trichloroacetic Acid
1.665 µg/L
No EPA limit set
worst single sample: 1.7 µg/L
2/3 SYR4 2017–2019
Antimony, Total
0.4000 µg/L 6.7%
of the EPA limit 6 µg/L
1/10 SYR4 2012–2019
Cyanide
3.5 µg/L 1.8%
of the EPA limit 200 µg/L
1/10 SYR4 2012–2019
Selenium
1.1 µg/L 2.2%
of the EPA limit 50 µg/L
1/9 SYR4 2012–2018
Toluene
0.6000 µg/L 0.1%
of the EPA limit 1000 µg/L
1/12 SYR4 2014–2019
56 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCadmiumCarbofuranCarbon TetrachlorideChlordaneDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneFluorideGlyphosateHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidNitriteOxamylPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneThallium, TotalTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
DAVID HOOGSTAD
Phone
570-443-7099

Frequently asked questions about Aqua Pa Midway

Is Aqua Pa Midway tap water safe to drink?

EPA monitoring detected 22 contaminants in Aqua Pa Midway's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Aqua Pa Midway's water?

EPA monitoring detected Copper, Nitrate, Barium, Chromium, TTHM, and others. The full list with the level and data source for each is above.

How many people does Aqua Pa Midway serve?

Aqua Pa Midway reports serving 2,450 people in Pennsylvania, per its EPA record.

Has Aqua Pa Midway had any water quality violations?

The EPA has 278 violations on file for Aqua Pa Midway, of which 4 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.