← Oklahoma

Tap water quality report

Tulsa Co W Imp Dist #14

EPA monitoring tested this supplier for 14 contaminants and detected 12. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

14
contaminants tested
12
detected
1,400
people served
0
health-based violations
Water source
SWP
Ownership
Local government
Counties served
Tulsa

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

0
health-based violations
39
violations on file
0
still open
ViolationTypeStatusPeriod
MON Monitoring Archived 2026-01-01 → 2026-01-31
MON Monitoring Archived 2026-01-01 → 2026-01-31
MR Monitoring Archived 2026-01-01 → 2026-01-31
MR Monitoring Archived 2026-01-01 → 2026-01-31
MR Monitoring Archived 2025-11-01 → 2025-11-30
MR Monitoring Archived 2025-11-01 → 2025-11-30
MON Monitoring Archived 2025-11-01 → 2025-11-30
MON Monitoring Archived 2025-11-01 → 2025-11-30
MR Monitoring Resolved 2025-03-01 → 2025-03-31
MR Monitoring Resolved 2025-03-01 → 2025-03-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the single worst sample on record — over 100% is worth reading, but is not by itself a violation. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
1280 µg/L 98%
of the EPA limit 1300 µg/L
48/60 SYR4 2013–2019
TTHM
56.9 µg/L 71%
of the EPA limit 80 µg/L
19/19 SYR4 2013–2019
Total Haloacetic Acids (HAA5)
23.4 µg/L 39%
of the EPA limit 60 µg/L
19/19 SYR4 2013–2019
Bromodichloromethane
21.6 µg/L
No EPA limit set
13/13 SYR4 2013–2019
Chloroform
22.2 µg/L
No EPA limit set
13/13 SYR4 2013–2019
Dibromoacetic Acid
4.34 µg/L
No EPA limit set
13/13 SYR4 2013–2019
Dibromochloromethane
15 µg/L
No EPA limit set
13/13 SYR4 2013–2019
Dichloroacetic Acid
11.5 µg/L
No EPA limit set
13/13 SYR4 2013–2019
Trichloroacetic Acid
10.2 µg/L
No EPA limit set
13/13 SYR4 2013–2019
Bromoform
4.18 µg/L
No EPA limit set
11/13 SYR4 2013–2019
Lead
0.0025 mg/L 17%
of the EPA limit 0.0150 mg/L
8/8 LCR 2025
Lead
88.7 µg/L 591%
of the EPA limit, in the worst sample — 15 µg/L
7/60 SYR4 2013–2019
2 contaminants tested, none detected
Monobromoacetic AcidMonochloroacetic Acid

Utility contact

Contact
TULSA CO W IMP DIST #14
Phone
918-245-1857
Email
waterdist14@tulsacoxmail.com

Frequently asked questions about Tulsa Co W Imp Dist #14

Is Tulsa Co W Imp Dist #14 tap water safe to drink?

EPA monitoring detected 12 contaminants in Tulsa Co W Imp Dist #14's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Tulsa Co W Imp Dist #14's water?

EPA monitoring detected Copper, TTHM, Total Haloacetic Acids (HAA5), Bromodichloromethane, Chloroform, and others. The full list with the level and data source for each is above.

How many people does Tulsa Co W Imp Dist #14 serve?

Tulsa Co W Imp Dist #14 reports serving 1,400 people in Oklahoma, per its EPA record.

Has Tulsa Co W Imp Dist #14 had any water quality violations?

The EPA has 39 violations on file for Tulsa Co W Imp Dist #14, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.