← Oklahoma

Tap water quality report

Texas County Rwd #1

EPA monitoring tested this supplier for 46 contaminants and detected 16. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

46
contaminants tested
16
detected
135
people served
28
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Texas

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

28
health-based violations
77
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2015-10-01 → 2015-10-31
MCL Health-based Resolved 2015-10-01 → 2015-10-31
MCL Health-based Resolved 2015-10-01 → 2015-10-31
MCL Health-based Resolved 2015-10-01 → 2015-10-31
MCL Health-based Resolved 2014-10-01 → 2014-10-31
MCL Health-based Resolved 2014-10-01 → 2014-10-31
MCL Health-based Resolved 2014-10-01 → 2014-10-31
MCL Health-based Resolved 2012-10-01 → 2012-12-31
MCL Health-based Resolved 2012-10-01 → 2012-12-31
MCL Health-based Resolved 2012-10-01 → 2012-12-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
4190 µg/L 42%
of the EPA limit 10000 µg/L
18/18 SYR4 2012–2018
Combined Uranium
8.8 µg/L 29%
of the EPA limit 30 µg/L
15/15 SYR4 2012–2019
Gross Beta Particle Activity
7.017 pCi/L
No EPA limit set
worst single sample: 7.08 pCi/L
15/15 SYR4 2012–2019
Copper
137.4 µg/L 11%
of the EPA limit 1300 µg/L
worst single sample: 140 µg/L
14/15 SYR4 2013–2019
Gross Alpha, Excl. Radon And U
5.905 pCi/L 39%
of the EPA limit 15 pCi/L
worst single sample: 6.1 pCi/L
14/15 SYR4 2012–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
14/14 LCR 2025
Combined Radium (-226 And -228)
1.4365 pCi/L 29%
of the EPA limit 5 pCi/L
worst single sample: 1.58 pCi/L
8/15 SYR4 2012–2019
Nitrate-Nitrite
3377 µg/L 34%
of the EPA limit 10000 µg/L
worst single sample: 3440 µg/L
8/8 SYR4 2013–2019
1,2-Dichloroethane
5.2935 µg/L 106%
of the EPA limit, at the 95th percentile of samples — 5 µg/L
worst single sample: 5.4 µg/L
4/16 SYR4 2012–2019
Benzene
25.2765 µg/L 506%
of the EPA limit, at the 95th percentile of samples — 5 µg/L
worst single sample: 28.5 µg/L
4/16 SYR4 2012–2019
Arsenic
5.68 µg/L 57%
of the EPA limit 10 µg/L
worst single sample: 5.7 µg/L
3/5 SYR4 2012–2019
Barium
81.94 µg/L 4.1%
of the EPA limit 2000 µg/L
worst single sample: 84.2 µg/L
3/3 SYR4 2012–2019
Fluoride
1403 µg/L 35%
of the EPA limit 4000 µg/L
worst single sample: 1410 µg/L
3/3 SYR4 2012–2019
Bromoform
1.84 µg/L
No EPA limit set
worst single sample: 1.9 µg/L
2/8 SYR4 2016–2019
Lead
2.4315 µg/L 16%
of the EPA limit 15 µg/L
worst single sample: 2.5 µg/L
2/15 SYR4 2013–2019
Xylenes, Total
3.43 µg/L 0%
of the EPA limit 10000 µg/L
1/16 SYR4 2012–2019
30 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DichloropropaneAntimony, TotalBeryllium, TotalBromodichloromethaneChlorobenzeneCyanideCadmiumCarbon TetrachlorideChloroformChromiumDichloromethaneDibromochloromethaneEthylbenzeneMercuryNitriteSeleniumStyreneTetrachloroethyleneThallium, TotalTolueneTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
TEXAS COUNTY RWD #1
Phone
580-651-9460
Email
txcorwd1@outlook.com

Frequently asked questions about Texas County Rwd #1

Is Texas County Rwd #1 tap water safe to drink?

EPA monitoring detected 16 contaminants in Texas County Rwd #1's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Texas County Rwd #1's water?

EPA monitoring detected Nitrate, Combined Uranium, Gross Beta Particle Activity, Copper, Gross Alpha, Excl. Radon And U, and others. The full list with the level and data source for each is above.

How many people does Texas County Rwd #1 serve?

Texas County Rwd #1 reports serving 135 people in Oklahoma, per its EPA record.

Has Texas County Rwd #1 had any water quality violations?

The EPA has 77 violations on file for Texas County Rwd #1, of which 28 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.