← Oklahoma

Tap water quality report

Mannford

EPA monitoring tested this supplier for 90 contaminants and detected 19. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

90
contaminants tested
19
detected
3,935
people served
673
health-based violations
Water source
Surface water
Ownership
Local government
Counties served
Creek

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

673
health-based violations
725
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2021-10-01 → 2021-12-31
MCL Health-based Resolved 2021-10-01 → 2021-12-31
MCL Health-based Resolved 2021-10-01 → 2021-12-31
MCL Health-based Resolved 2010-04-01 → 2010-06-30
MCL Health-based Resolved 2010-04-01 → 2010-06-30
MCL Health-based Resolved 2010-04-01 → 2010-06-30
MCL Health-based Resolved 2010-04-01 → 2010-06-30
MCL Health-based Resolved 2010-04-01 → 2010-06-30
MCL Health-based Resolved 2010-01-01 → 2010-03-31
MCL Health-based Resolved 2010-01-01 → 2010-03-31

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
Pfba 0.0076 µg/L 2/4 2024

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the single worst sample on record — over 100% is worth reading, but is not by itself a violation. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Bromodichloromethane
42.5 µg/L
No EPA limit set
59/59 SYR4 2012–2019
Chloroform
88.1 µg/L
No EPA limit set
59/59 SYR4 2012–2019
Dibromochloromethane
23.9 µg/L
No EPA limit set
59/59 SYR4 2012–2019
Dichloroacetic Acid
40.4 µg/L
No EPA limit set
58/58 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
90.5 µg/L 151%
of the EPA limit, in the worst sample — 60 µg/L
58/58 SYR4 2012–2019
Trichloroacetic Acid
44.7 µg/L
No EPA limit set
58/58 SYR4 2012–2019
TTHM
137 µg/L 171%
of the EPA limit, in the worst sample — 80 µg/L
57/57 SYR4 2012–2019
Dibromoacetic Acid
4.11 µg/L
No EPA limit set
52/58 SYR4 2012–2019
Bromoform
3.7 µg/L
No EPA limit set
35/59 SYR4 2012–2019
Copper
99 µg/L 7.6%
of the EPA limit 1300 µg/L
27/50 SYR4 2013–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
14/14 LCR 2025
Monobromoacetic Acid
1.94 µg/L
No EPA limit set
13/58 SYR4 2012–2019
Monochloroacetic Acid
5.68 µg/L
No EPA limit set
10/58 SYR4 2012–2019
Nitrate-Nitrite
210 µg/L 2.1%
of the EPA limit 10000 µg/L
4/18 SYR4 2012–2019
Barium
43.1 µg/L 2.2%
of the EPA limit 2000 µg/L
1/1 SYR4 2013
Combined Radium (-226 And -228)
0.1300 pCi/L 2.6%
of the EPA limit 5 pCi/L
1/1 SYR4 2016
Gross Beta Particle Activity
3.55 pCi/L
No EPA limit set
1/1 SYR4 2016
Hexachlorocyclopentadiene
0.0200 µg/L 0%
of the EPA limit 50 µg/L
1/1 SYR4 2018
71 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalArsenicBhc-GammaBenzeneBeryllium, TotalChlorobenzeneCadmiumCarbofuranCarbon TetrachlorideChromiumCombined UraniumDichloromethaneEndrinEthylbenzeneFluorideGlyphosateGross Alpha, Excl. Radon And UHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideLeadMercuryMethoxychlorNetfosaaNfdhaNmefosaaOxamylPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaSeleniumStyreneTetrachloroethyleneThallium, TotalTolueneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
MANNFORD
Phone
918-865-4314
Email
mannfordwater@cimtel.net

Frequently asked questions about Mannford

Is Mannford tap water safe to drink?

EPA monitoring detected 19 contaminants in Mannford's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Mannford's water?

EPA monitoring detected Bromodichloromethane, Chloroform, Dibromochloromethane, Dichloroacetic Acid, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.

How many people does Mannford serve?

Mannford reports serving 3,935 people in Oklahoma, per its EPA record.

Has Mannford had any water quality violations?

The EPA has 725 violations on file for Mannford, of which 673 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.