Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Archived | 2025-10-01 → 2025-12-31 |
| TT | Health-based | Archived | 2025-10-01 → 2025-12-31 |
| TT | Health-based | Archived | 2025-10-01 → 2025-12-31 |
| TT | Health-based | Archived | 2025-07-01 → 2025-09-30 |
| TT | Health-based | Archived | 2025-07-01 → 2025-09-30 |
| TT | Health-based | Archived | 2025-04-01 → 2025-06-30 |
| TT | Health-based | Archived | 2025-04-01 → 2025-06-30 |
| TT | Health-based | Archived | 2025-04-01 → 2025-06-30 |
| TT | Health-based | Archived | 2025-01-01 → 2025-03-31 |
| TT | Health-based | Archived | 2025-01-01 → 2025-03-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromodichloromethane | 20.2 µg/L No EPA limit set | 60/60 | SYR4 | 2012–2019 |
| Chloroform | 406 µg/L No EPA limit set | 60/60 | SYR4 | 2012–2019 |
| TTHM | 421.6 µg/L 527% of the EPA limit, in the worst sample — 80 µg/L | 60/60 | SYR4 | 2012–2019 |
| Copper | 129.62 µg/L 10% of the EPA limit 1300 µg/L | 59/75 | SYR4 | 2012–2017 |
| Total Haloacetic Acids (HAA5) | 642 µg/L 1070% of the EPA limit, in the worst sample — 60 µg/L | 53/60 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 246 µg/L No EPA limit set | 51/60 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 396 µg/L No EPA limit set | 48/60 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 31.6 µg/L No EPA limit set | 25/60 | SYR4 | 2012–2019 |
| Lead | 0.0033 mg/L 22% of the EPA limit 0.0150 mg/L | 23/23 | LCR | 2025 |
| Lead | 12.84 µg/L 86% of the EPA limit 15 µg/L | 23/75 | SYR4 | 2012–2017 |
| Dibromochloromethane | 2.48 µg/L No EPA limit set | 19/60 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 370 µg/L 3.7% of the EPA limit 10000 µg/L | 16/18 | SYR4 | 2012–2019 |
| Bromoform | 1.25 µg/L No EPA limit set | 2/60 | SYR4 | 2012–2019 |
| Barium | 26.9 µg/L 1.3% of the EPA limit 2000 µg/L | 1/1 | SYR4 | 2012 |
| Combined Radium (-226 And -228) | 1.77 pCi/L 35% of the EPA limit 5 pCi/L | 1/2 | SYR4 | 2013–2019 |
| Gross Alpha, Excl. Radon And U | 0.6980 pCi/L 4.7% of the EPA limit 15 pCi/L | 1/2 | SYR4 | 2013–2019 |
| Gross Beta Particle Activity | 3.45 pCi/L No EPA limit set | 1/2 | SYR4 | 2013–2019 |
| Monobromoacetic Acid | 2.68 µg/L No EPA limit set | 1/60 | SYR4 | 2012–2019 |
32 contaminants tested, none detected
Utility contact
Frequently asked questions about Weleetka Public Works Authority
Is Weleetka Public Works Authority tap water safe to drink?
EPA monitoring detected 18 contaminants in Weleetka Public Works Authority's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Weleetka Public Works Authority's water?
EPA monitoring detected Bromodichloromethane, Chloroform, TTHM, Copper, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.
How many people does Weleetka Public Works Authority serve?
Weleetka Public Works Authority reports serving 998 people in Oklahoma, per its EPA record.
Has Weleetka Public Works Authority had any water quality violations?
The EPA has 1787 violations on file for Weleetka Public Works Authority, of which 1347 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.