← Ohio

Tap water quality report

Waynesville Village

EPA monitoring tested this supplier for 98 contaminants and detected 17. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

98
contaminants tested
17
detected
4,100
people served
12
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Warren

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

12
health-based violations
43
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2024-05-01 → 2024-05-31
MCL Health-based Resolved 2024-05-01 → 2024-05-31
MCL Health-based Resolved 2024-05-01 → 2024-05-31
MCL Health-based Resolved 2024-05-01 → 2024-05-31
MCL Health-based Resolved 1993-06-01 → 1993-06-30
MCL Health-based Resolved 1993-06-01 → 1993-06-30
MCL Health-based Resolved 1993-06-01 → 1993-06-30
MCL Health-based Resolved 1993-06-01 → 1993-06-30
MCL Health-based Resolved 1993-06-01 → 1993-06-30
MCL Health-based Resolved 1993-06-01 → 1993-06-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the single worst sample on record — over 100% is worth reading, but is not by itself a violation. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
547 µg/L 42%
of the EPA limit 1300 µg/L
60/60 SYR4 2012–2019
Lead
31.6 µg/L 211%
of the EPA limit, in the worst sample — 15 µg/L
21/60 SYR4 2012–2019
Lead
0.0016 mg/L 11%
of the EPA limit 0.0150 mg/L
20/20 LCR 2025
Nitrate
3600 µg/L 36%
of the EPA limit 10000 µg/L
16/16 SYR4 2012–2019
Bromodichloromethane
7.3 µg/L
No EPA limit set
14/14 SYR4 2013–2019
Bromoform
1.9 µg/L
No EPA limit set
14/14 SYR4 2013–2019
Chloroform
6.2 µg/L
No EPA limit set
14/14 SYR4 2013–2019
Dibromochloromethane
6.3 µg/L
No EPA limit set
14/14 SYR4 2013–2019
TTHM
21.7 µg/L 27%
of the EPA limit 80 µg/L
14/14 SYR4 2013–2019
Dibromoacetic Acid
2.3 µg/L
No EPA limit set
11/14 SYR4 2013–2019
Dichloroacetic Acid
3 µg/L
No EPA limit set
11/14 SYR4 2013–2019
Trichloroacetic Acid
2.7 µg/L
No EPA limit set
9/14 SYR4 2013–2019
Nitrate-Nitrite
3600 µg/L 36%
of the EPA limit 10000 µg/L
8/8 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
6.5 µg/L 11%
of the EPA limit 60 µg/L
4/14 SYR4 2013–2019
Barium
79.8 µg/L 4%
of the EPA limit 2000 µg/L
3/3 SYR4 2013–2019
Monobromoacetic Acid
2.2 µg/L
No EPA limit set
2/14 SYR4 2013–2019
Combined Radium (-226 And -228)
1.6 pCi/L 32%
of the EPA limit 5 pCi/L
1/1 SYR4 2013
81 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalArsenicAsbestosAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChromiumDichloromethaneDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDiquatEndothallEthylbenzeneFluorideGlyphosateHfpo-DaLassoMercuryMethoxychlorMonochloroacetic AcidNetfosaaNfdhaNmefosaaNitriteOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)TrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
COPELAND, GARY
Phone
513-897-8015
Email
gcopeland@waynesville-ohio.org

Frequently asked questions about Waynesville Village

Is Waynesville Village tap water safe to drink?

EPA monitoring detected 17 contaminants in Waynesville Village's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Waynesville Village's water?

EPA monitoring detected Copper, Lead, Lead, Nitrate, Bromodichloromethane, and others. The full list with the level and data source for each is above.

How many people does Waynesville Village serve?

Waynesville Village reports serving 4,100 people in Ohio, per its EPA record.

Has Waynesville Village had any water quality violations?

The EPA has 43 violations on file for Waynesville Village, of which 12 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.