← Ohio

Tap water quality report

Trumbull Co. - Bazetta/Champion

EPA monitoring tested this supplier for 44 contaminants and detected 14. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

44
contaminants tested
14
detected
8,270
people served
4
health-based violations
Water source
SWP
Ownership
Local government
Counties served
Trumbull

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

4
health-based violations
9
violations on file
1
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2014-07-01 → 2014-09-30
MCL Health-based Resolved 2014-07-01 → 2014-09-30
MCL Health-based Resolved 2014-07-01 → 2014-09-30
MCL Health-based Resolved 2014-07-01 → 2014-09-30
Other Monitoring Unaddressed 2018-12-04
MR Monitoring Resolved 1995-01-01
MR Monitoring Resolved 1995-01-01
MR Monitoring Resolved 1995-01-01
MR Monitoring Resolved 1995-01-01

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
Pfba 0.0054 µg/L 2/4 2024

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Bromodichloromethane
14.71 µg/L
No EPA limit set
worst single sample: 15.2 µg/L
60/60 SYR4 2012–2019
Chloroform
93.335 µg/L
No EPA limit set
worst single sample: 115 µg/L
60/60 SYR4 2012–2019
TTHM
107.25 µg/L 134%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 132 µg/L
60/60 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
67.67 µg/L 113%
of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 89.2 µg/L
60/60 SYR4 2012–2019
Trichloroacetic Acid
29.205 µg/L
No EPA limit set
worst single sample: 31.3 µg/L
60/60 SYR4 2012–2019
Dichloroacetic Acid
39.08 µg/L
No EPA limit set
worst single sample: 52.1 µg/L
59/60 SYR4 2012–2019
Dibromochloromethane
1.9 µg/L
No EPA limit set
worst single sample: 11.4 µg/L
55/60 SYR4 2012–2019
Copper
51.08 µg/L 3.9%
of the EPA limit 1300 µg/L
worst single sample: 54.2 µg/L
25/45 SYR4 2014–2017
Monochloroacetic Acid
12.42 µg/L
No EPA limit set
worst single sample: 17.8 µg/L
24/60 SYR4 2012–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
18/18 LCR 2025
Lead
54.524 µg/L 363%
of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 59.5 µg/L
3/45 SYR4 2014–2017
Dibromoacetic Acid
3.59 µg/L
No EPA limit set
worst single sample: 3.68 µg/L
2/60 SYR4 2012–2019
Monobromoacetic Acid
1.086 µg/L
No EPA limit set
worst single sample: 1.09 µg/L
2/60 SYR4 2012–2019
30 contaminants tested, none detected
11Cl-PF3OUdS4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaBromoformHfpo-DaNetfosaaNfdhaNmefosaaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaLithium

Utility contact

Contact
PREBONICK, DANIEL
Phone
330-675-7860
Email
daniel.prebonick@co.trumbull.oh.us

Frequently asked questions about Trumbull Co. - Bazetta/Champion

Is Trumbull Co. - Bazetta/Champion tap water safe to drink?

EPA monitoring detected 14 contaminants in Trumbull Co. - Bazetta/Champion's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Trumbull Co. - Bazetta/Champion's water?

EPA monitoring detected Bromodichloromethane, Chloroform, TTHM, Total Haloacetic Acids (HAA5), Trichloroacetic Acid, and others. The full list with the level and data source for each is above.

How many people does Trumbull Co. - Bazetta/Champion serve?

Trumbull Co. - Bazetta/Champion reports serving 8,270 people in Ohio, per its EPA record.

Has Trumbull Co. - Bazetta/Champion had any water quality violations?

The EPA has 9 violations on file for Trumbull Co. - Bazetta/Champion, of which 4 are health-based (a contaminant limit or required treatment was breached) and 1 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.