Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2017-04-01 → 2017-06-30 |
| MCL | Health-based | Resolved | 2017-04-01 → 2017-06-30 |
| MCL | Health-based | Resolved | 2017-04-01 → 2017-06-30 |
| MCL | Health-based | Resolved | 2017-04-01 → 2017-06-30 |
| Other | Monitoring | Unaddressed | 2021-10-27 |
| MR | Monitoring | Resolved | 2004-05-01 → 2004-05-31 |
| MR | Monitoring | Resolved | 2004-05-01 → 2004-05-31 |
| MR | Monitoring | Resolved | 2004-05-01 → 2004-05-31 |
| MR | Monitoring | Resolved | 2004-05-01 → 2004-05-31 |
| MR | Monitoring | Resolved | 2004-05-01 → 2004-05-31 |
PFAS detected
| Contaminant | Max | Detection rate | Period |
|---|---|---|---|
| Pfba | 0.0055 µg/L | 1/4 | 2024 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromodichloromethane | 14.06 µg/L No EPA limit set
worst single sample: 16.8 µg/L | 67/67 | SYR4 | 2012–2019 |
| Chloroform | 73.7 µg/L No EPA limit set
worst single sample: 108.2 µg/L | 67/67 | SYR4 | 2012–2019 |
| TTHM | 86.98 µg/L 109% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 126.6 µg/L | 67/67 | SYR4 | 2012–2019 |
| Dibromochloromethane | 1.975 µg/L No EPA limit set
worst single sample: 2 µg/L | 66/67 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 35.86 µg/L No EPA limit set
worst single sample: 42.6 µg/L | 62/62 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 73.185 µg/L 122% of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 91 µg/L | 62/62 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 34.6 µg/L No EPA limit set
worst single sample: 44.6 µg/L | 61/62 | SYR4 | 2012–2019 |
| Copper | 541 µg/L 42% of the EPA limit 1300 µg/L
worst single sample: 700 µg/L | 50/73 | SYR4 | 2013–2019 |
| Monochloroacetic Acid | 7.42 µg/L No EPA limit set
worst single sample: 22.3 µg/L | 39/62 | SYR4 | 2012–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 19/19 | LCR | 2025 |
| Dibromoacetic Acid | 1.4 µg/L No EPA limit set | 7/62 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 1.575 µg/L No EPA limit set
worst single sample: 1.6 µg/L | 6/62 | SYR4 | 2012–2019 |
| Lead | 31.8 µg/L 212% of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 38 µg/L | 5/71 | SYR4 | 2013–2019 |
30 contaminants tested, none detected
Frequently asked questions about Aqua Ohio - Masury
Is Aqua Ohio - Masury tap water safe to drink?
EPA monitoring detected 14 contaminants in Aqua Ohio - Masury's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Aqua Ohio - Masury's water?
EPA monitoring detected Bromodichloromethane, Chloroform, TTHM, Dibromochloromethane, Dichloroacetic Acid, and others. The full list with the level and data source for each is above.
How many people does Aqua Ohio - Masury serve?
Aqua Ohio - Masury reports serving 4,019 people, per its EPA record.
Has Aqua Ohio - Masury had any water quality violations?
The EPA has 23 violations on file for Aqua Ohio - Masury, of which 4 are health-based (a contaminant limit or required treatment was breached) and 1 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.