Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2022-06-25 |
| TT | Health-based | Resolved | 2022-06-25 |
| TT | Health-based | Resolved | 2022-06-25 |
| TT | Health-based | Resolved | 2022-06-25 |
| Other | Monitoring | Unaddressed | 2023-12-29 |
| Other | Monitoring | Unaddressed | 2020-01-15 |
| MR | Monitoring | Resolved | 1997-07-01 → 1997-12-31 |
| MR | Monitoring | Resolved | 1997-07-01 → 1997-12-31 |
| MR | Monitoring | Resolved | 1997-07-01 → 1997-12-31 |
| MR | Monitoring | Resolved | 1997-07-01 → 1997-12-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 182.5 µg/L 14% of the EPA limit 1300 µg/L
worst single sample: 310 µg/L | 76/80 | SYR4 | 2013–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 18/18 | LCR | 2023 |
| TTHM | 4.535 µg/L 5.7% of the EPA limit 80 µg/L
worst single sample: 4.56 µg/L | 11/14 | SYR4 | 2013–2019 |
| Bromodichloromethane | 0.9010 µg/L No EPA limit set
worst single sample: 0.9100 µg/L | 10/17 | SYR4 | 2013–2019 |
| Bromoform | 2.4525 µg/L No EPA limit set
worst single sample: 2.97 µg/L | 10/17 | SYR4 | 2013–2019 |
| Dibromoacetic Acid | 2.46 µg/L No EPA limit set | 10/14 | SYR4 | 2013–2019 |
| Dibromochloromethane | 0.9250 µg/L No EPA limit set
worst single sample: 0.9700 µg/L | 10/17 | SYR4 | 2013–2019 |
| Fluoride | 828.5 µg/L 21% of the EPA limit 4000 µg/L
worst single sample: 860 µg/L | 10/10 | SYR4 | 2013–2019 |
| Chloroform | 1.3075 µg/L No EPA limit set
worst single sample: 1.36 µg/L | 8/17 | SYR4 | 2013–2019 |
| Barium | 237 µg/L 12% of the EPA limit 2000 µg/L
worst single sample: 243 µg/L | 7/10 | SYR4 | 2013–2019 |
| Total Haloacetic Acids (HAA5) | 5.1575 µg/L 8.6% of the EPA limit 60 µg/L
worst single sample: 5.3 µg/L | 6/14 | SYR4 | 2013–2019 |
| Lithium | 35.8 µg/L No EPA limit set | 6/6 | UCMR-5 | 2023 |
| Nitrate-Nitrite | 902.2 µg/L 9% of the EPA limit 10000 µg/L
worst single sample: 913 µg/L | 5/20 | SYR4 | 2012–2019 |
| Lead | 14.337 µg/L 96% of the EPA limit 15 µg/L
worst single sample: 14.67 µg/L | 4/80 | SYR4 | 2013–2019 |
| Combined Radium (-226 And -228) | 3.93 pCi/L 79% of the EPA limit 5 pCi/L
worst single sample: 4.1 pCi/L | 3/3 | SYR4 | 2013–2015 |
| Dichloroacetic Acid | 1.275 µg/L No EPA limit set
worst single sample: 1.3 µg/L | 3/14 | SYR4 | 2013–2019 |
| Monochloroacetic Acid | 2.27 µg/L No EPA limit set | 1/14 | SYR4 | 2013–2019 |
| Trichloroacetic Acid | 1.49 µg/L No EPA limit set | 1/14 | SYR4 | 2013–2019 |
| Xylenes, Total | 0.5600 µg/L 0% of the EPA limit 10000 µg/L | 1/16 | SYR4 | 2013–2019 |
65 contaminants tested, none detected
Utility contact
Frequently asked questions about Cortland City
Is Cortland City tap water safe to drink?
EPA monitoring detected 19 contaminants in Cortland City's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Cortland City's water?
EPA monitoring detected Copper, Lead, TTHM, Bromodichloromethane, Bromoform, and others. The full list with the level and data source for each is above.
How many people does Cortland City serve?
Cortland City reports serving 7,105 people in Ohio, per its EPA record.
Has Cortland City had any water quality violations?
The EPA has 129 violations on file for Cortland City, of which 4 are health-based (a contaminant limit or required treatment was breached) and 2 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.