Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MR | Monitoring | Resolved | 2000-07-01 → 2000-12-31 |
| MR | Monitoring | Resolved | 2000-07-01 → 2000-12-31 |
| MR | Monitoring | Resolved | 2000-07-01 → 2000-12-31 |
| MR | Monitoring | Resolved | 2000-07-01 → 2000-12-31 |
| MR | Monitoring | Resolved | 2000-07-01 → 2000-12-31 |
| MR | Monitoring | Resolved | 2000-07-01 → 2000-12-31 |
| MR | Monitoring | Resolved | 1994-07-01 → 1994-12-31 |
| MR | Monitoring | Resolved | 1994-07-01 → 1994-12-31 |
| MR | Monitoring | Resolved | 1994-07-01 → 1994-12-31 |
| MR | Monitoring | Resolved | 1994-07-01 → 1994-12-31 |
PFAS detected
| Contaminant | Max | Detection rate | Period |
|---|---|---|---|
| Pfba | 0.0071 µg/L | 1/4 | 2023 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Chlorite | 962 µg/L 96% of the EPA limit 1000 µg/L | 286/286 | SYR4 | 2012–2019 |
| Chloroform | 85.8 µg/L No EPA limit set | 139/140 | SYR4 | 2012–2019 |
| Bromodichloromethane | 22.9 µg/L No EPA limit set | 138/139 | SYR4 | 2012–2019 |
| Dibromochloromethane | 5.7 µg/L No EPA limit set | 135/140 | SYR4 | 2012–2019 |
| TTHM | 109 µg/L 136% of the EPA limit, in the worst sample — 80 µg/L | 133/133 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 114 µg/L 190% of the EPA limit, in the worst sample — 60 µg/L | 133/133 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 47.5 µg/L No EPA limit set | 132/132 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 65.6 µg/L No EPA limit set | 132/132 | SYR4 | 2012–2019 |
| Copper | 580 µg/L 45% of the EPA limit 1300 µg/L | 120/120 | SYR4 | 2012–2019 |
| Nitrate | 560 µg/L 5.6% of the EPA limit 10000 µg/L | 110/192 | SYR4 | 2012–2019 |
| Lead | 17 µg/L 113% of the EPA limit, in the worst sample — 15 µg/L | 54/120 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 7.04 µg/L No EPA limit set | 34/130 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 560 µg/L 5.6% of the EPA limit 10000 µg/L | 33/49 | SYR4 | 2012–2016 |
| Dibromoacetic Acid | 10.9 µg/L No EPA limit set | 26/133 | SYR4 | 2012–2019 |
| Lead | 0.0037 mg/L 25% of the EPA limit 0.0150 mg/L | 21/21 | LCR | 2025 |
| Monobromoacetic Acid | 16.5 µg/L No EPA limit set | 14/133 | SYR4 | 2012–2019 |
| Bromoform | 0.9100 µg/L No EPA limit set | 13/140 | SYR4 | 2012–2019 |
| Fluoride | 1230 µg/L 31% of the EPA limit 4000 µg/L | 8/8 | SYR4 | 2012–2019 |
| Barium | 29 µg/L 1.5% of the EPA limit 2000 µg/L | 7/8 | SYR4 | 2012–2019 |
| Arsenic | 1.07 µg/L 11% of the EPA limit 10 µg/L | 1/8 | SYR4 | 2012–2019 |
| Chromium | 1.36 µg/L 1.4% of the EPA limit 100 µg/L | 1/8 | SYR4 | 2012–2019 |
| Ethylbenzene | 1.42 µg/L 0.2% of the EPA limit 700 µg/L | 1/9 | SYR4 | 2012–2019 |
| Xylenes, Total | 8.93 µg/L 0.1% of the EPA limit 10000 µg/L | 1/9 | SYR4 | 2012–2019 |
61 contaminants tested, none detected
Utility contact
Frequently asked questions about Ravenna City
Is Ravenna City tap water safe to drink?
EPA monitoring detected 24 contaminants in Ravenna City's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Ravenna City's water?
EPA monitoring detected Chlorite, Chloroform, Bromodichloromethane, Dibromochloromethane, TTHM, and others. The full list with the level and data source for each is above.
How many people does Ravenna City serve?
Ravenna City reports serving 16,000 people in Ohio, per its EPA record.
Has Ravenna City had any water quality violations?
The EPA has 12 violations on file for Ravenna City, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.