Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Archived | 2014-05-01 → 2014-05-31 |
| MCL | Health-based | Archived | 2014-05-01 → 2014-05-31 |
| MCL | Health-based | Archived | 2014-05-01 → 2014-05-31 |
| Other | Monitoring | Unaddressed | 2025-11-19 |
| Other | Monitoring | Unaddressed | 2025-02-14 |
| Other | Monitoring | Unaddressed | 2024-09-12 |
| MR | Monitoring | Resolved | 2023-01-01 → 2023-12-31 |
| MR | Monitoring | Resolved | 2023-01-01 → 2023-12-31 |
| MR | Monitoring | Resolved | 2023-01-01 → 2023-12-31 |
| Other | Monitoring | Resolved | 2021-07-01 |
PFAS detected
| Contaminant | Max | Detection rate | Period |
|---|---|---|---|
| Pfpea | 0.0031 µg/L | 2/2 | 2024 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromodichloromethane | 31.7 µg/L No EPA limit set | 118/118 | SYR4 | 2012–2019 |
| Chloroform | 44.8 µg/L No EPA limit set | 118/118 | SYR4 | 2012–2019 |
| Dibromochloromethane | 22.6 µg/L No EPA limit set | 118/118 | SYR4 | 2012–2019 |
| TTHM | 91.1 µg/L 114% of the EPA limit, in the worst sample — 80 µg/L | 118/118 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 12.7 µg/L No EPA limit set | 116/116 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 25.6 µg/L 43% of the EPA limit 60 µg/L | 116/116 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 11.5 µg/L No EPA limit set | 114/116 | SYR4 | 2012–2019 |
| Bromoform | 3.5 µg/L No EPA limit set | 109/118 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 5 µg/L No EPA limit set | 102/116 | SYR4 | 2012–2019 |
| Copper | 1030 µg/L 79% of the EPA limit 1300 µg/L | 26/61 | SYR4 | 2014–2017 |
| Nitrate | 230 µg/L 2.3% of the EPA limit 10000 µg/L | 24/32 | SYR4 | 2012–2019 |
| Lead | 0.00060 mg/L 4% of the EPA limit 0.0150 mg/L | 19/19 | LCR | 2025 |
| Nitrate-Nitrite | 230 µg/L 2.3% of the EPA limit 10000 µg/L | 12/16 | SYR4 | 2012–2019 |
| Barium | 161 µg/L 8.1% of the EPA limit 2000 µg/L | 6/6 | SYR4 | 2013–2019 |
| Fluoride | 1000 µg/L 25% of the EPA limit 4000 µg/L | 6/6 | SYR4 | 2013–2019 |
| Lead | 10 µg/L 67% of the EPA limit 15 µg/L | 3/61 | SYR4 | 2014–2017 |
| Monobromoacetic Acid | 1.4 µg/L No EPA limit set | 3/116 | SYR4 | 2012–2019 |
| Combined Radium (-226 And -228) | 2.1 pCi/L 42% of the EPA limit 5 pCi/L | 1/1 | SYR4 | 2019 |
64 contaminants tested, none detected
Utility contact
Frequently asked questions about Pike Water, Inc.-Plant
Is Pike Water, Inc.-Plant tap water safe to drink?
EPA monitoring detected 19 contaminants in Pike Water, Inc.-Plant's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Pike Water, Inc.-Plant's water?
EPA monitoring detected Bromodichloromethane, Chloroform, Dibromochloromethane, TTHM, Dichloroacetic Acid, and others. The full list with the level and data source for each is above.
How many people does Pike Water, Inc.-Plant serve?
Pike Water, Inc.-Plant reports serving 15,487 people in Ohio, per its EPA record.
Has Pike Water, Inc.-Plant had any water quality violations?
The EPA has 56 violations on file for Pike Water, Inc.-Plant, of which 3 are health-based (a contaminant limit or required treatment was breached) and 5 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.