Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2008-02-01 → 2008-02-29 |
| TT | Health-based | Resolved | 2008-02-01 → 2008-02-29 |
| TT | Health-based | Resolved | 2008-02-01 → 2008-02-29 |
| TT | Health-based | Resolved | 2008-02-01 → 2008-02-29 |
| MCL | Health-based | Resolved | 1995-07-01 → 1995-07-31 |
| MCL | Health-based | Resolved | 1995-07-01 → 1995-07-31 |
| MCL | Health-based | Resolved | 1995-07-01 → 1995-07-31 |
| MCL | Health-based | Resolved | 1995-07-01 → 1995-07-31 |
| TT | Health-based | Resolved | 1993-10-01 → 1993-10-31 |
| TT | Health-based | Resolved | 1993-10-01 → 1993-10-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 260 µg/L 20% of the EPA limit 1300 µg/L | 149/156 | SYR4 | 2013–2019 |
| Bromodichloromethane | 21.5 µg/L No EPA limit set | 130/130 | SYR4 | 2012–2019 |
| Chloroform | 79.4 µg/L No EPA limit set | 130/130 | SYR4 | 2012–2019 |
| Dibromochloromethane | 9.1 µg/L No EPA limit set | 128/128 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 26.8 µg/L No EPA limit set | 128/128 | SYR4 | 2012–2019 |
| TTHM | 106 µg/L 133% of the EPA limit, in the worst sample — 80 µg/L | 128/128 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 37.5 µg/L 63% of the EPA limit 60 µg/L | 127/127 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 16.1 µg/L No EPA limit set | 127/127 | SYR4 | 2012–2019 |
| Nitrate | 1070 µg/L 11% of the EPA limit 10000 µg/L | 100/192 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 3.1 µg/L No EPA limit set | 97/123 | SYR4 | 2012–2019 |
| Bromoform | 1.7 µg/L No EPA limit set | 95/126 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 1070 µg/L 11% of the EPA limit 10000 µg/L | 50/96 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 4.7 µg/L No EPA limit set | 36/128 | SYR4 | 2012–2019 |
| Lead | 0.0021 mg/L 14% of the EPA limit 0.0150 mg/L | 27/27 | LCR | 2025 |
| Lead | 13 µg/L 87% of the EPA limit 15 µg/L | 20/119 | SYR4 | 2013–2019 |
| Fluoride | 1270 µg/L 32% of the EPA limit 4000 µg/L | 8/8 | SYR4 | 2012–2019 |
| Atrazine | 0.2600 µg/L 8.7% of the EPA limit 3 µg/L | 6/10 | SYR4 | 2012–2019 |
| Barium | 13 µg/L 0.7% of the EPA limit 2000 µg/L | 5/8 | SYR4 | 2012–2019 |
| Simazine | 0.0680 µg/L 1.7% of the EPA limit 4 µg/L | 1/10 | SYR4 | 2012–2019 |
64 contaminants tested, none detected
Utility contact
Frequently asked questions about Findlay City
Is Findlay City tap water safe to drink?
EPA monitoring detected 19 contaminants in Findlay City's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Findlay City's water?
EPA monitoring detected Copper, Bromodichloromethane, Chloroform, Dibromochloromethane, Dichloroacetic Acid, and others. The full list with the level and data source for each is above.
How many people does Findlay City serve?
Findlay City reports serving 54,040 people in Ohio, per its EPA record.
Has Findlay City had any water quality violations?
The EPA has 44 violations on file for Findlay City, of which 24 are health-based (a contaminant limit or required treatment was breached) and 1 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.