← Ohio

Tap water quality report

New Miami Village

EPA monitoring tested this supplier for 82 contaminants and detected 14. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

82
contaminants tested
14
detected
3,200
people served
4
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Butler

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

4
health-based violations
113
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2000-08-01 → 2000-08-31
MCL Health-based Resolved 2000-08-01 → 2000-08-31
MCL Health-based Resolved 2000-08-01 → 2000-08-31
MCL Health-based Resolved 2000-08-01 → 2000-08-31
MON Monitoring Resolved 2017-05-01 → 2017-05-31
MON Monitoring Resolved 2017-05-01 → 2017-05-31
MON Monitoring Resolved 2017-05-01 → 2017-05-31
MON Monitoring Resolved 2017-05-01 → 2017-05-31
MR Monitoring Resolved 2002-01-01 → 2002-06-30
MR Monitoring Resolved 2002-01-01 → 2002-06-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the single worst sample on record — over 100% is worth reading, but is not by itself a violation. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
334 µg/L 26%
of the EPA limit 1300 µg/L
23/40 SYR4 2014–2019
Lead
0.0011 mg/L 7.3%
of the EPA limit 0.0150 mg/L
21/21 LCR 2025
Bromodichloromethane
6 µg/L
No EPA limit set
14/14 SYR4 2013–2019
Bromoform
3.25 µg/L
No EPA limit set
14/14 SYR4 2013–2019
Chloroform
3.8 µg/L
No EPA limit set
14/14 SYR4 2013–2019
Dibromochloromethane
6.84 µg/L
No EPA limit set
14/14 SYR4 2013–2019
TTHM
18.8 µg/L 24%
of the EPA limit 80 µg/L
14/14 SYR4 2013–2019
Dibromoacetic Acid
2.4 µg/L
No EPA limit set
8/14 SYR4 2013–2019
Dichloroacetic Acid
2.5 µg/L
No EPA limit set
6/14 SYR4 2013–2019
Nitrate
390 µg/L 3.9%
of the EPA limit 10000 µg/L
6/16 SYR4 2012–2019
Lead
8.8 µg/L 59%
of the EPA limit 15 µg/L
3/40 SYR4 2014–2019
Nitrate-Nitrite
390 µg/L 3.9%
of the EPA limit 10000 µg/L
3/8 SYR4 2012–2019
Barium
117 µg/L 5.9%
of the EPA limit 2000 µg/L
2/2 SYR4 2014–2017
Fluoride
900 µg/L 23%
of the EPA limit 4000 µg/L
2/2 SYR4 2014–2017
68 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalArsenicAtrazineBenzeneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbon TetrachlorideChromiumDichloromethaneEthylbenzeneHfpo-DaLassoMercuryMonobromoacetic AcidMonochloroacetic AcidNetfosaaNfdhaNmefosaaNitritePfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Haloacetic Acids (HAA5)Trichloroacetic AcidTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
COOK, JAMIE
Phone
513-894-8668
Email
JAMIE.CK1@GMAIL.COM

Frequently asked questions about New Miami Village

Is New Miami Village tap water safe to drink?

EPA monitoring detected 14 contaminants in New Miami Village's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in New Miami Village's water?

EPA monitoring detected Copper, Lead, Bromodichloromethane, Bromoform, Chloroform, and others. The full list with the level and data source for each is above.

How many people does New Miami Village serve?

New Miami Village reports serving 3,200 people in Ohio, per its EPA record.

Has New Miami Village had any water quality violations?

The EPA has 113 violations on file for New Miami Village, of which 4 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.