Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MON | Monitoring | Resolved | 2020-01-01 → 2020-01-31 |
| MON | Monitoring | Resolved | 2020-01-01 → 2020-01-31 |
| MON | Monitoring | Resolved | 2020-01-01 → 2020-01-31 |
| MON | Monitoring | Resolved | 2020-01-01 → 2020-01-31 |
| MON | Monitoring | Resolved | 2018-01-01 → 2018-01-31 |
| MON | Monitoring | Resolved | 2018-01-01 → 2018-01-31 |
| MON | Monitoring | Archived | 2017-03-01 → 2017-03-31 |
| MON | Monitoring | Archived | 2017-01-01 → 2017-01-31 |
| MR | Monitoring | Resolved | 2015-01-01 |
| MR | Monitoring | Resolved | 2015-01-01 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 1444.5 µg/L 14% of the EPA limit 10000 µg/L
worst single sample: 1490 µg/L | 28/28 | SYR4 | 2012–2019 |
| Bromodichloromethane | 4.5955 µg/L No EPA limit set
worst single sample: 6.8 µg/L | 24/24 | SYR4 | 2012–2019 |
| Chloroform | 2.5495 µg/L No EPA limit set
worst single sample: 2.71 µg/L | 24/24 | SYR4 | 2012–2019 |
| Dibromochloromethane | 7.317 µg/L No EPA limit set
worst single sample: 11 µg/L | 24/24 | SYR4 | 2012–2019 |
| TTHM | 18.72 µg/L 23% of the EPA limit 80 µg/L
worst single sample: 29.3 µg/L | 24/24 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 4.966 µg/L 8.3% of the EPA limit 60 µg/L
worst single sample: 7.23 µg/L | 17/24 | SYR4 | 2012–2019 |
| Lead | 0.0025 mg/L 17% of the EPA limit 0.0150 mg/L | 16/16 | LCR | 2025 |
| Bromoform | 6.064 µg/L No EPA limit set
worst single sample: 8.78 µg/L | 15/24 | SYR4 | 2012–2019 |
| Barium | 316.8 µg/L 16% of the EPA limit 2000 µg/L
worst single sample: 322 µg/L | 14/14 | SYR4 | 2012–2019 |
| Chromium | 7.475 µg/L 7.5% of the EPA limit 100 µg/L
worst single sample: 7.8 µg/L | 14/14 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 1405.5 µg/L 14% of the EPA limit 10000 µg/L
worst single sample: 1490 µg/L | 14/14 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 1.86 µg/L No EPA limit set
worst single sample: 1.92 µg/L | 13/24 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 3.667 µg/L No EPA limit set
worst single sample: 4.36 µg/L | 12/24 | SYR4 | 2012–2019 |
| Combined Radium (-226 And -228) | 1.099 pCi/L 22% of the EPA limit 5 pCi/L
worst single sample: 1.149 pCi/L | 6/6 | SYR4 | 2016–2018 |
| Combined Uranium | 7.95 µg/L 27% of the EPA limit 30 µg/L
worst single sample: 8.9 µg/L | 6/6 | SYR4 | 2016–2018 |
| Gross Beta Particle Activity | 8.64 pCi/L No EPA limit set
worst single sample: 9.21 pCi/L | 6/6 | SYR4 | 2016–2018 |
| Cyanide | 42.6 µg/L 21% of the EPA limit 200 µg/L
worst single sample: 46 µg/L | 5/12 | SYR4 | 2012–2018 |
| Fluoride | 135.5 µg/L 3.4% of the EPA limit 4000 µg/L
worst single sample: 140 µg/L | 4/14 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 1.3815 µg/L No EPA limit set
worst single sample: 1.41 µg/L | 4/24 | SYR4 | 2012–2019 |
| Gross Alpha, Excl. Radon And U | 0.7800 pCi/L 5.2% of the EPA limit 15 pCi/L
worst single sample: 0.8000 pCi/L | 2/6 | SYR4 | 2016–2018 |
| 2,4-D | 3.02 µg/L 4.3% of the EPA limit 70 µg/L | 1/11 | SYR4 | 2014–2017 |
| Monochloroacetic Acid | 1.73 µg/L No EPA limit set | 1/24 | SYR4 | 2012–2019 |
| Simazine | 0.1400 µg/L 3.5% of the EPA limit 4 µg/L | 1/11 | SYR4 | 2014–2017 |
52 contaminants tested, none detected
Utility contact
Frequently asked questions about North Castle Water District #4
Is North Castle Water District #4 tap water safe to drink?
EPA monitoring detected 23 contaminants in North Castle Water District #4's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in North Castle Water District #4's water?
EPA monitoring detected Nitrate, Bromodichloromethane, Chloroform, Dibromochloromethane, TTHM, and others. The full list with the level and data source for each is above.
How many people does North Castle Water District #4 serve?
North Castle Water District #4 reports serving 1,225 people in New York, per its EPA record.
Has North Castle Water District #4 had any water quality violations?
The EPA has 12 violations on file for North Castle Water District #4, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.