Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2025-05-23 |
| TT | Health-based | Resolved | 2025-05-23 |
| TT | Health-based | Resolved | 2025-05-23 |
| TT | Health-based | Resolved | 2025-05-23 |
| MCL | Health-based | Resolved | 2017-07-01 → 2017-09-30 |
| MCL | Health-based | Resolved | 2017-07-01 → 2017-09-30 |
| MCL | Health-based | Resolved | 2017-07-01 → 2017-09-30 |
| MCL | Health-based | Resolved | 2017-07-01 → 2017-09-30 |
| MCL | Health-based | Resolved | 2016-07-01 → 2016-09-30 |
| MCL | Health-based | Resolved | 2016-07-01 → 2016-09-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromodichloromethane | 30.09 µg/L No EPA limit set
worst single sample: 37 µg/L | 44/44 | SYR4 | 2012–2019 |
| Dibromochloromethane | 38.35 µg/L No EPA limit set
worst single sample: 40.6 µg/L | 44/44 | SYR4 | 2012–2019 |
| TTHM | 105.78 µg/L 132% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 182 µg/L | 44/44 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 36.0485 µg/L 60% of the EPA limit 60 µg/L
worst single sample: 45.4 µg/L | 44/44 | SYR4 | 2012–2019 |
| Chloroform | 40.39 µg/L No EPA limit set
worst single sample: 137 µg/L | 43/44 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 13.39 µg/L No EPA limit set
worst single sample: 22.8 µg/L | 43/44 | SYR4 | 2012–2019 |
| Bromoform | 30.4 µg/L No EPA limit set
worst single sample: 38.5 µg/L | 41/44 | SYR4 | 2012–2019 |
| Lead | 0.0616 mg/L 411% above the EPA limit of 0.0150 mg/L | 40/40 | LCR | 2026 |
| Dibromoacetic Acid | 13.28 µg/L No EPA limit set
worst single sample: 16 µg/L | 37/44 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 16.405 µg/L No EPA limit set
worst single sample: 22.6 µg/L | 32/44 | SYR4 | 2012–2019 |
| Combined Radium (-226 And -228) | 3.976 pCi/L 80% of the EPA limit 5 pCi/L
worst single sample: 4.68 pCi/L | 17/17 | SYR4 | 2013–2019 |
| Gross Alpha, Excl. Radon And U | 19.9 pCi/L 133% of the EPA limit, at the 95th percentile of samples — 15 pCi/L
worst single sample: 25.6 pCi/L | 16/17 | SYR4 | 2013–2019 |
| Combined Uranium | 16.4004 µg/L 55% of the EPA limit 30 µg/L
worst single sample: 19.668 µg/L | 15/17 | SYR4 | 2013–2019 |
| Monobromoacetic Acid | 4.152 µg/L No EPA limit set
worst single sample: 4.68 µg/L | 13/44 | SYR4 | 2012–2019 |
| Gross Beta Particle Activity | 8.436 pCi/L No EPA limit set
worst single sample: 8.94 pCi/L | 10/11 | SYR4 | 2016–2019 |
| Barium | 34.945 µg/L 1.7% of the EPA limit 2000 µg/L
worst single sample: 35.5 µg/L | 2/3 | SYR4 | 2012–2018 |
| Monochloroacetic Acid | 4.004 µg/L No EPA limit set
worst single sample: 4.11 µg/L | 2/44 | SYR4 | 2012–2019 |
| Nitrate | 350 µg/L 3.5% of the EPA limit 10000 µg/L | 2/16 | SYR4 | 2012–2019 |
| Cyanide | 165 µg/L 83% of the EPA limit 200 µg/L | 1/3 | SYR4 | 2012–2018 |
| Nitrate-Nitrite | 350 µg/L 3.5% of the EPA limit 10000 µg/L | 1/8 | SYR4 | 2012–2019 |
55 contaminants tested, none detected
Utility contact
Frequently asked questions about Oakridge Water District
Is Oakridge Water District tap water safe to drink?
EPA monitoring detected 20 contaminants in Oakridge Water District's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Oakridge Water District's water?
EPA monitoring detected Bromodichloromethane, Dibromochloromethane, TTHM, Total Haloacetic Acids (HAA5), Chloroform, and others. The full list with the level and data source for each is above.
How many people does Oakridge Water District serve?
Oakridge Water District reports serving 892 people in New York, per its EPA record.
Has Oakridge Water District had any water quality violations?
The EPA has 56 violations on file for Oakridge Water District, of which 20 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.