← New York

Tap water quality report

Harvey School

EPA monitoring tested this supplier for 74 contaminants and detected 20. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

74
contaminants tested
20
detected
510
people served
4
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Westchester

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

4
health-based violations
293
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2010-09-01 → 2010-09-30
MCL Health-based Resolved 2010-09-01 → 2010-09-30
MCL Health-based Resolved 2010-09-01 → 2010-09-30
MCL Health-based Resolved 2010-09-01 → 2010-09-30
MON Monitoring Resolved 2023-10-01 → 2023-10-31
MON Monitoring Resolved 2023-10-01 → 2023-10-31
MON Monitoring Resolved 2023-10-01 → 2023-10-31
MON Monitoring Resolved 2023-10-01 → 2023-10-31
MR Monitoring Resolved 2023-01-01 → 2023-12-31
MR Monitoring Resolved 2023-01-01 → 2023-12-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
5670 µg/L 57%
of the EPA limit 10000 µg/L
worst single sample: 7140 µg/L
52/52 SYR4 2012–2019
Nitrate-Nitrite
5565 µg/L 56%
of the EPA limit 10000 µg/L
worst single sample: 7140 µg/L
26/26 SYR4 2012–2019
Bromodichloromethane
3.36 µg/L
No EPA limit set
worst single sample: 4 µg/L
25/25 SYR4 2012–2019
Dibromochloromethane
6.244 µg/L
No EPA limit set
worst single sample: 9.1 µg/L
25/25 SYR4 2012–2019
TTHM
15.32 µg/L 19%
of the EPA limit 80 µg/L
worst single sample: 21.7 µg/L
25/25 SYR4 2012–2019
Bromoform
7.195 µg/L
No EPA limit set
worst single sample: 8 µg/L
22/25 SYR4 2012–2019
Lead
0.0010 mg/L 6.7%
of the EPA limit 0.0150 mg/L
22/22 LCR 2025
Total Haloacetic Acids (HAA5)
5.08 µg/L 8.5%
of the EPA limit 60 µg/L
worst single sample: 6.1 µg/L
18/22 SYR4 2012–2019
Chloroform
1.76 µg/L
No EPA limit set
worst single sample: 1.9 µg/L
15/25 SYR4 2012–2019
Dibromoacetic Acid
4.16 µg/L
No EPA limit set
worst single sample: 5 µg/L
15/22 SYR4 2012–2019
Combined Uranium
28.25 µg/L 94%
of the EPA limit 30 µg/L
worst single sample: 31.7 µg/L
11/12 SYR4 2013–2019
Gross Alpha, Excl. Radon And U
8.43 pCi/L 56%
of the EPA limit 15 pCi/L
worst single sample: 9.2 pCi/L
8/12 SYR4 2013–2019
Dichloroacetic Acid
1.6 µg/L
No EPA limit set
7/22 SYR4 2012–2019
Barium
641 µg/L 32%
of the EPA limit 2000 µg/L
worst single sample: 800 µg/L
6/6 SYR4 2013–2019
Combined Radium (-226 And -228)
3.05 pCi/L 61%
of the EPA limit 5 pCi/L
worst single sample: 3.4 pCi/L
6/12 SYR4 2013–2019
Trichloroacetic Acid
1.6 µg/L
No EPA limit set
worst single sample: 1.7 µg/L
5/22 SYR4 2012–2019
Di(2-ethylhexyl) Phthalate
6.83 µg/L 114%
of the EPA limit, at the 95th percentile of samples — 6 µg/L
worst single sample: 6.9 µg/L
3/10 SYR4 2012–2018
Arsenic
1 µg/L 10%
of the EPA limit 10 µg/L
1/6 SYR4 2013–2019
Fluoride
200 µg/L 5%
of the EPA limit 4000 µg/L
1/6 SYR4 2013–2019
Selenium
1 µg/L 2%
of the EPA limit 50 µg/L
1/6 SYR4 2013–2019
54 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDinosebEthylene DibromideEndrinEthylbenzeneHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidNitriteOxamylPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
KNAUER, WILLIAM J.
Phone
914-232-3161
Email
wknauer@harveyschool.org

Frequently asked questions about Harvey School

Is Harvey School tap water safe to drink?

EPA monitoring detected 20 contaminants in Harvey School's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Harvey School's water?

EPA monitoring detected Nitrate, Nitrate-Nitrite, Bromodichloromethane, Dibromochloromethane, TTHM, and others. The full list with the level and data source for each is above.

How many people does Harvey School serve?

Harvey School reports serving 510 people in New York, per its EPA record.

Has Harvey School had any water quality violations?

The EPA has 293 violations on file for Harvey School, of which 4 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.