← New York

Tap water quality report

North Castle Water District #2

EPA monitoring tested this supplier for 75 contaminants and detected 20. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

75
contaminants tested
20
detected
1,200
people served
0
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Westchester

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

0
health-based violations
5
violations on file
0
still open
ViolationTypeStatusPeriod
MON Monitoring Resolved 2020-01-01 → 2020-01-31
MON Monitoring Resolved 2020-01-01 → 2020-01-31
MON Monitoring Resolved 2020-01-01 → 2020-01-31
MON Monitoring Resolved 2020-01-01 → 2020-01-31
MR Monitoring Resolved 1993-11-01 → 1993-11-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
2330 µg/L 23%
of the EPA limit 10000 µg/L
16/16 SYR4 2012–2019
Bromodichloromethane
8.901 µg/L
No EPA limit set
worst single sample: 8.94 µg/L
14/14 SYR4 2012–2019
Chloroform
12.955 µg/L
No EPA limit set
worst single sample: 15.1 µg/L
14/14 SYR4 2012–2019
Dibromochloromethane
7.159 µg/L
No EPA limit set
worst single sample: 7.25 µg/L
14/14 SYR4 2012–2019
TTHM
27.2845 µg/L 34%
of the EPA limit 80 µg/L
worst single sample: 28.5 µg/L
14/14 SYR4 2012–2019
Bromoform
1.647 µg/L
No EPA limit set
worst single sample: 1.68 µg/L
12/14 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
9.444 µg/L 16%
of the EPA limit 60 µg/L
worst single sample: 9.84 µg/L
12/14 SYR4 2012–2019
Lead
0.0035 mg/L 23%
of the EPA limit 0.0150 mg/L
10/10 LCR 2025
Trichloroacetic Acid
2.5325 µg/L
No EPA limit set
worst single sample: 2.6 µg/L
10/14 SYR4 2012–2019
Dichloroacetic Acid
6.286 µg/L
No EPA limit set
worst single sample: 6.51 µg/L
9/14 SYR4 2012–2019
Barium
124.6 µg/L 6.2%
of the EPA limit 2000 µg/L
worst single sample: 133 µg/L
8/8 SYR4 2012–2019
Chromium
6.06 µg/L 6.1%
of the EPA limit 100 µg/L
worst single sample: 6.6 µg/L
7/8 SYR4 2012–2019
Nitrate-Nitrite
2000 µg/L 20%
of the EPA limit 10000 µg/L
worst single sample: 2330 µg/L
7/7 SYR4 2012–2019
Dibromoacetic Acid
2.1275 µg/L
No EPA limit set
worst single sample: 2.21 µg/L
6/14 SYR4 2012–2019
Combined Radium (-226 And -228)
1.0656 pCi/L 21%
of the EPA limit 5 pCi/L
worst single sample: 1.077 pCi/L
5/5 SYR4 2016–2018
Gross Beta Particle Activity
4.822 pCi/L
No EPA limit set
worst single sample: 4.98 pCi/L
5/5 SYR4 2016–2018
Di(2-ethylhexyl) Phthalate
1.36 µg/L 23%
of the EPA limit 6 µg/L
4/7 SYR4 2014–2017
Cyanide
31.385 µg/L 16%
of the EPA limit 200 µg/L
worst single sample: 33 µg/L
2/7 SYR4 2012–2018
Combined Uranium
1.6 µg/L 5.3%
of the EPA limit 30 µg/L
1/5 SYR4 2016–2018
Gross Alpha, Excl. Radon And U
0.6710 pCi/L 4.5%
of the EPA limit 15 pCi/L
1/4 SYR4 2016–2018
55 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalArsenicAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCadmiumCarbofuranCarbon TetrachlorideChlordaneDichloromethaneDalaponDi(2-ethylhexyl) AdipateDinosebEthylene DibromideEndrinEthylbenzeneFluorideHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidNitriteOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
RENDE, JOSEPH
Phone
914-273-3000
Email
supervisor@northcastleny.com

Frequently asked questions about North Castle Water District #2

Is North Castle Water District #2 tap water safe to drink?

EPA monitoring detected 20 contaminants in North Castle Water District #2's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in North Castle Water District #2's water?

EPA monitoring detected Nitrate, Bromodichloromethane, Chloroform, Dibromochloromethane, TTHM, and others. The full list with the level and data source for each is above.

How many people does North Castle Water District #2 serve?

North Castle Water District #2 reports serving 1,200 people in New York, per its EPA record.

Has North Castle Water District #2 had any water quality violations?

The EPA has 5 violations on file for North Castle Water District #2, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.