← New York

Tap water quality report

High Ridge Water Company

EPA monitoring tested this supplier for 72 contaminants and detected 14. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

72
contaminants tested
14
detected
65
people served
0
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Ulster

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

0
health-based violations
10
violations on file
0
still open
ViolationTypeStatusPeriod
Other Monitoring Resolved 2004-07-01
Other Monitoring Resolved 2004-07-01
Other Monitoring Resolved 2004-07-01
MR Monitoring Resolved 2000-06-01 → 2000-06-30
MR Monitoring Resolved 1996-10-01
MR Monitoring Resolved 1996-10-01
MR Monitoring Resolved 1996-01-01 → 1996-12-31
MR Monitoring Resolved 1996-01-01 → 1996-12-31
MR Monitoring Resolved 1996-01-01 → 1996-12-31
MR Monitoring Resolved 1994-01-01 → 1994-12-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
696 µg/L 7%
of the EPA limit 10000 µg/L
12/16 SYR4 2012–2019
Lead
0.0052 mg/L 34%
of the EPA limit 0.0150 mg/L
9/9 LCR 2025
Bromodichloromethane
16.845 µg/L
No EPA limit set
worst single sample: 17.3 µg/L
8/8 SYR4 2012–2019
Chloroform
17.14 µg/L
No EPA limit set
worst single sample: 18.4 µg/L
8/8 SYR4 2012–2019
Dibromoacetic Acid
4.885 µg/L
No EPA limit set
worst single sample: 5.2 µg/L
8/8 SYR4 2012–2019
Dibromochloromethane
15.2 µg/L
No EPA limit set
8/8 SYR4 2012–2019
TTHM
47.935 µg/L 60%
of the EPA limit 80 µg/L
worst single sample: 49.3 µg/L
8/8 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
20.08 µg/L 33%
of the EPA limit 60 µg/L
worst single sample: 20.5 µg/L
8/8 SYR4 2012–2019
Trichloroacetic Acid
9.02 µg/L
No EPA limit set
worst single sample: 10.7 µg/L
8/8 SYR4 2012–2019
Bromoform
3.31 µg/L
No EPA limit set
worst single sample: 3.4 µg/L
7/8 SYR4 2012–2019
Dichloroacetic Acid
7.84 µg/L
No EPA limit set
worst single sample: 8.2 µg/L
7/8 SYR4 2012–2019
Monobromoacetic Acid
7.6 µg/L
No EPA limit set
worst single sample: 8 µg/L
3/8 SYR4 2012–2019
Barium
95.5 µg/L 4.8%
of the EPA limit 2000 µg/L
worst single sample: 96 µg/L
2/2 SYR4 2014–2017
Fluoride
500 µg/L 13%
of the EPA limit 4000 µg/L
2/2 SYR4 2014–2017
58 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalArsenicAsbestosAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumCombined Radium (-226 And -228)Combined UraniumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebEthylene DibromideEndrinEthylbenzeneHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonochloroacetic AcidOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
VOGT, JEFF
Phone
845-331-2201
Email
vogty123@aol.com

Frequently asked questions about High Ridge Water Company

Is High Ridge Water Company tap water safe to drink?

EPA monitoring detected 14 contaminants in High Ridge Water Company's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in High Ridge Water Company's water?

EPA monitoring detected Nitrate, Lead, Bromodichloromethane, Chloroform, Dibromoacetic Acid, and others. The full list with the level and data source for each is above.

How many people does High Ridge Water Company serve?

High Ridge Water Company reports serving 65 people in New York, per its EPA record.

Has High Ridge Water Company had any water quality violations?

The EPA has 10 violations on file for High Ridge Water Company, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.