← New York

Tap water quality report

Rosendale Water District

EPA monitoring tested this supplier for 71 contaminants and detected 14. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

71
contaminants tested
14
detected
2,200
people served
1
health-based violations
Water source
Surface water
Ownership
Local government
Counties served
Ulster

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

1
health-based violations
275
violations on file
0
still open
ViolationTypeStatusPeriod
TT Health-based Archived 2000-01-01 → 2000-12-31
MR Monitoring Resolved 2015-05-01 → 2015-05-31
MR Monitoring Resolved 2015-05-01 → 2015-05-31
MR Monitoring Resolved 2015-05-01 → 2015-05-31
MR Monitoring Resolved 2014-01-01 → 2014-03-31
MR Monitoring Resolved 2014-01-01 → 2014-03-31
MR Monitoring Resolved 2014-01-01 → 2014-03-31
MR Monitoring Resolved 2014-01-01 → 2014-03-31
MR Monitoring Resolved 2014-01-01 → 2014-03-31
MR Monitoring Resolved 2014-01-01 → 2014-03-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Bromodichloromethane
12 µg/L
No EPA limit set
worst single sample: 39 µg/L
27/27 SYR4 2012–2019
Chloroform
29 µg/L
No EPA limit set
worst single sample: 31 µg/L
27/27 SYR4 2012–2019
Dibromochloromethane
4.1 µg/L
No EPA limit set
worst single sample: 4.4 µg/L
27/27 SYR4 2012–2019
TTHM
45.7 µg/L 57%
of the EPA limit 80 µg/L
worst single sample: 69 µg/L
27/27 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
15.7 µg/L 26%
of the EPA limit 60 µg/L
worst single sample: 21 µg/L
27/27 SYR4 2012–2019
Trichloroacetic Acid
7.87 µg/L
No EPA limit set
worst single sample: 11 µg/L
27/27 SYR4 2012–2019
Dichloroacetic Acid
8.14 µg/L
No EPA limit set
worst single sample: 8.5 µg/L
25/27 SYR4 2012–2019
Nitrate
2800 µg/L 28%
of the EPA limit 10000 µg/L
16/16 SYR4 2012–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
12/12 LCR 2023
Barium
34.65 µg/L 1.7%
of the EPA limit 2000 µg/L
worst single sample: 35 µg/L
8/8 SYR4 2012–2019
Bromoform
1.98 µg/L
No EPA limit set
worst single sample: 2.4 µg/L
7/27 SYR4 2012–2019
Monochloroacetic Acid
11.9 µg/L
No EPA limit set
worst single sample: 13 µg/L
3/27 SYR4 2012–2019
Dibromoacetic Acid
1 µg/L
No EPA limit set
1/27 SYR4 2012–2019
Monobromoacetic Acid
1 µg/L
No EPA limit set
1/27 SYR4 2012–2019
57 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalArsenicAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumCombined Radium (-226 And -228)Combined UraniumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebEthylene DibromideEndrinEthylbenzeneFluorideHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
ROSENDALE TOWN SUPERVISOR

Frequently asked questions about Rosendale Water District

Is Rosendale Water District tap water safe to drink?

EPA monitoring detected 14 contaminants in Rosendale Water District's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Rosendale Water District's water?

EPA monitoring detected Bromodichloromethane, Chloroform, Dibromochloromethane, TTHM, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.

How many people does Rosendale Water District serve?

Rosendale Water District reports serving 2,200 people in New York, per its EPA record.

Has Rosendale Water District had any water quality violations?

The EPA has 275 violations on file for Rosendale Water District, of which 1 is health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.