Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| RPT | Monitoring | Resolved | 2024-07-01 |
| RPT | Monitoring | Resolved | 2024-07-01 |
| MON | Monitoring | Resolved | 2020-10-01 → 2020-12-31 |
| MON | Monitoring | Resolved | 2020-10-01 → 2020-12-31 |
| MON | Monitoring | Resolved | 2020-04-01 → 2020-06-30 |
| Other | Monitoring | Resolved | 2010-01-01 → 2010-01-31 |
| Other | Monitoring | Resolved | 2010-01-01 → 2010-01-31 |
| Other | Monitoring | Resolved | 2010-01-01 → 2010-01-31 |
| Other | Monitoring | Resolved | 2009-11-01 → 2009-11-30 |
| Other | Monitoring | Resolved | 2009-11-01 → 2009-11-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 1600 µg/L 16% of the EPA limit 10000 µg/L | 16/16 | SYR4 | 2012–2019 |
| Barium | 253 µg/L 13% of the EPA limit 2000 µg/L | 4/4 | SYR4 | 2013–2019 |
| Bromodichloromethane | 0.9800 µg/L No EPA limit set | 3/3 | SYR4 | 2014–2017 |
| Bromoform | 2.3 µg/L No EPA limit set | 3/3 | SYR4 | 2014–2017 |
| Chloroform | 1.3 µg/L No EPA limit set | 3/3 | SYR4 | 2014–2017 |
| Lead | 0.0056 mg/L 37% of the EPA limit 0.0150 mg/L | 3/3 | LCR | 2019 |
| Dibromoacetic Acid | 1.5 µg/L No EPA limit set | 2/2 | SYR4 | 2014–2017 |
| Dibromochloromethane | 1.9 µg/L No EPA limit set | 2/3 | SYR4 | 2014–2017 |
| TTHM | 5.1 µg/L 6.4% of the EPA limit 80 µg/L | 2/2 | SYR4 | 2014–2017 |
| Total Haloacetic Acids (HAA5) | 2.3 µg/L 3.8% of the EPA limit 60 µg/L | 2/2 | SYR4 | 2014–2017 |
| Arsenic | 2.7 µg/L 27% of the EPA limit 10 µg/L | 1/4 | SYR4 | 2013–2019 |
| Combined Radium (-226 And -228) | 0.1500 pCi/L 3% of the EPA limit 5 pCi/L | 1/1 | SYR4 | 2013 |
| Combined Uranium | 6.705 µg/L 22% of the EPA limit 30 µg/L | 1/1 | SYR4 | 2013 |
| Dichloroacetic Acid | 1.2 µg/L No EPA limit set | 1/2 | SYR4 | 2014–2017 |
| Gross Beta Particle Activity | 3.4 pCi/L No EPA limit set | 1/1 | SYR4 | 2013 |
59 contaminants tested, none detected
Utility contact
Frequently asked questions about Sunrise Community Mhp
Is Sunrise Community Mhp tap water safe to drink?
EPA monitoring detected 15 contaminants in Sunrise Community Mhp's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Sunrise Community Mhp's water?
EPA monitoring detected Nitrate, Barium, Bromodichloromethane, Bromoform, Chloroform, and others. The full list with the level and data source for each is above.
How many people does Sunrise Community Mhp serve?
Sunrise Community Mhp reports serving 100 people in New York, per its EPA record.
Has Sunrise Community Mhp had any water quality violations?
The EPA has 21 violations on file for Sunrise Community Mhp, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.