Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2017-04-01 → 2017-06-30 |
| MCL | Health-based | Resolved | 2017-04-01 → 2017-06-30 |
| MR | Monitoring | Unaddressed | 2024-01-25 |
| MR | Monitoring | Unaddressed | 2023-07-01 |
| MON | Monitoring | Archived | 2022-07-01 → 2022-07-31 |
| MR | Monitoring | Resolved | 2010-01-01 → 2010-12-31 |
| MR | Monitoring | Resolved | 2010-01-01 → 2010-12-31 |
| MR | Monitoring | Resolved | 2010-01-01 → 2010-12-31 |
| MR | Monitoring | Resolved | 2010-01-01 → 2010-12-31 |
| MR | Monitoring | Resolved | 2010-01-01 → 2010-12-31 |
PFAS detected
| Contaminant | Max | Detection rate | Period |
|---|---|---|---|
| Pfpea | 0.0041 µg/L | 2/10 | 2025 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Chloroform | 93.31 µg/L No EPA limit set
worst single sample: 132 µg/L | 67/67 | SYR4 | 2012–2019 |
| Bromodichloromethane | 3.685 µg/L No EPA limit set
worst single sample: 4.74 µg/L | 66/67 | SYR4 | 2012–2019 |
| TTHM | 96.875 µg/L 121% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 137 µg/L | 66/66 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 39.76 µg/L No EPA limit set
worst single sample: 177 µg/L | 65/65 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 84.78 µg/L 141% of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 178 µg/L | 65/65 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 47.8 µg/L No EPA limit set
worst single sample: 53.5 µg/L | 61/65 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 7.865 µg/L No EPA limit set
worst single sample: 11.4 µg/L | 32/65 | SYR4 | 2012–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 20/20 | LCR | 2023 |
| Nitrate | 1190 µg/L 12% of the EPA limit 10000 µg/L | 18/32 | SYR4 | 2012–2019 |
| Barium | 185 µg/L 9.3% of the EPA limit 2000 µg/L
worst single sample: 210 µg/L | 11/11 | SYR4 | 2012–2019 |
| Dibromochloromethane | 3.04 µg/L No EPA limit set | 10/67 | SYR4 | 2012–2019 |
| Copper | 16.295 µg/L 1.3% of the EPA limit 1300 µg/L
worst single sample: 17 µg/L | 4/5 | SYR4 | 2016–2017 |
| Monobromoacetic Acid | 1.085 µg/L No EPA limit set
worst single sample: 1.1 µg/L | 4/65 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 1.93 µg/L No EPA limit set
worst single sample: 2 µg/L | 3/65 | SYR4 | 2012–2019 |
| Bromoform | 0.6550 µg/L No EPA limit set
worst single sample: 0.6600 µg/L | 2/67 | SYR4 | 2012–2019 |
| Arsenic | 1 µg/L 10% of the EPA limit 10 µg/L | 1/11 | SYR4 | 2012–2019 |
| Combined Radium (-226 And -228) | 0.6370 pCi/L 13% of the EPA limit 5 pCi/L | 1/1 | SYR4 | 2016 |
| Combined Uranium | 0.1743 µg/L 0.6% of the EPA limit 30 µg/L | 1/1 | SYR4 | 2016 |
87 contaminants tested, none detected
Utility contact
Frequently asked questions about Liberty Village
Is Liberty Village tap water safe to drink?
EPA monitoring detected 19 contaminants in Liberty Village's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Liberty Village's water?
EPA monitoring detected Chloroform, Bromodichloromethane, TTHM, Dichloroacetic Acid, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.
How many people does Liberty Village serve?
Liberty Village reports serving 3,900 people in New York, per its EPA record.
Has Liberty Village had any water quality violations?
The EPA has 53 violations on file for Liberty Village, of which 2 are health-based (a contaminant limit or required treatment was breached) and 2 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.