← New York

Tap water quality report

Mountain View Meadows Mhp

EPA monitoring tested this supplier for 72 contaminants and detected 17. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

72
contaminants tested
17
detected
125
people served
20
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Sullivan

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

20
health-based violations
40
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2023-01-01 → 2023-03-31
MCL Health-based Resolved 2023-01-01 → 2023-03-31
MCL Health-based Resolved 2023-01-01 → 2023-03-31
MCL Health-based Resolved 2022-10-01 → 2022-12-31
MCL Health-based Resolved 2022-10-01 → 2022-12-31
MCL Health-based Resolved 2022-10-01 → 2022-12-31
MCL Health-based Resolved 2022-07-01 → 2022-09-30
MCL Health-based Resolved 2022-07-01 → 2022-09-30
MCL Health-based Resolved 2022-04-01 → 2022-06-30
MCL Health-based Resolved 2022-04-01 → 2022-06-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
1570 µg/L 16%
of the EPA limit 10000 µg/L
worst single sample: 1890 µg/L
48/48 SYR4 2012–2019
Lead
0.0047 mg/L 31%
of the EPA limit 0.0150 mg/L
8/8 LCR 2017
Barium
200.1 µg/L 10%
of the EPA limit 2000 µg/L
worst single sample: 201 µg/L
7/9 SYR4 2012–2018
Arsenic
4.55 µg/L 45%
of the EPA limit 10 µg/L
worst single sample: 4.6 µg/L
6/9 SYR4 2012–2018
TTHM
5.12 µg/L 6.4%
of the EPA limit 80 µg/L
worst single sample: 5.78 µg/L
4/9 SYR4 2013–2019
Combined Radium (-226 And -228)
0.5980 pCi/L 12%
of the EPA limit 5 pCi/L
worst single sample: 0.6221 pCi/L
3/3 SYR4 2016
Combined Uranium
1.4265 µg/L 4.8%
of the EPA limit 30 µg/L
worst single sample: 1.43 µg/L
3/3 SYR4 2016
Dibromochloromethane
1.901 µg/L
No EPA limit set
worst single sample: 2.03 µg/L
3/9 SYR4 2013–2019
Fluoride
164.1 µg/L 4.1%
of the EPA limit 4000 µg/L
worst single sample: 165 µg/L
3/9 SYR4 2012–2018
Gross Alpha, Excl. Radon And U
1.896 pCi/L 13%
of the EPA limit 15 pCi/L
worst single sample: 1.9 pCi/L
3/3 SYR4 2016
Bromodichloromethane
1.818 µg/L
No EPA limit set
worst single sample: 1.88 µg/L
2/9 SYR4 2013–2019
Chloroform
1.8065 µg/L
No EPA limit set
worst single sample: 1.87 µg/L
2/9 SYR4 2013–2019
Dichloroacetic Acid
2.3875 µg/L
No EPA limit set
worst single sample: 2.45 µg/L
2/9 SYR4 2013–2019
Total Haloacetic Acids (HAA5)
5.14 µg/L 8.6%
of the EPA limit 60 µg/L
worst single sample: 5.3 µg/L
2/9 SYR4 2013–2019
Trichloroacetic Acid
1.079 µg/L
No EPA limit set
worst single sample: 1.09 µg/L
2/9 SYR4 2013–2019
Dibromoacetic Acid
1.76 µg/L
No EPA limit set
1/9 SYR4 2013–2019
cis-1,2-Dichloroethylene
1 µg/L 1.4%
of the EPA limit 70 µg/L
1/3 SYR4 2015
55 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalBromoformChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebEthylene DibromideEndrinEthylbenzeneHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
SHIMER, DENNIS R
Phone
607-786-0918
Email
drshimer@stny.rr.com

Frequently asked questions about Mountain View Meadows Mhp

Is Mountain View Meadows Mhp tap water safe to drink?

EPA monitoring detected 17 contaminants in Mountain View Meadows Mhp's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Mountain View Meadows Mhp's water?

EPA monitoring detected Nitrate, Lead, Barium, Arsenic, TTHM, and others. The full list with the level and data source for each is above.

How many people does Mountain View Meadows Mhp serve?

Mountain View Meadows Mhp reports serving 125 people in New York, per its EPA record.

Has Mountain View Meadows Mhp had any water quality violations?

The EPA has 40 violations on file for Mountain View Meadows Mhp, of which 20 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.