← New York

Tap water quality report

Mount Ebo Ws

EPA monitoring tested this supplier for 45 contaminants and detected 18. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

45
contaminants tested
18
detected
1,500
people served
0
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Putnam

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

0
health-based violations
2
violations on file
0
still open
ViolationTypeStatusPeriod
MR Monitoring Resolved 1994-07-01
MR Monitoring Archived 1994-01-01 → 1994-06-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the single worst sample on record — over 100% is worth reading, but is not by itself a violation. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
300 µg/L 3%
of the EPA limit 10000 µg/L
18/18 SYR4 2012–2015
Barium
97 µg/L 4.9%
of the EPA limit 2000 µg/L
6/6 SYR4 2012–2015
Chloroform
97 µg/L
No EPA limit set
6/6 SYR4 2012–2015
Bromodichloromethane
3.4 µg/L
No EPA limit set
5/5 SYR4 2012–2015
Lead
0.0021 mg/L 14%
of the EPA limit 0.0150 mg/L
5/5 LCR 2024
Bromoform
1.6 µg/L
No EPA limit set
4/4 SYR4 2012–2015
Dibromochloromethane
2.9 µg/L
No EPA limit set
4/4 SYR4 2012–2015
TTHM
8.2 µg/L 10%
of the EPA limit 80 µg/L
4/4 SYR4 2012–2015
Total Haloacetic Acids (HAA5)
5.3 µg/L 8.8%
of the EPA limit 60 µg/L
3/4 SYR4 2012–2015
Combined Uranium
4.1 µg/L 14%
of the EPA limit 30 µg/L
2/2 SYR4 2014
Dibromoacetic Acid
1.4 µg/L
No EPA limit set
2/4 SYR4 2012–2015
Dichloroacetic Acid
1.2 µg/L
No EPA limit set
2/4 SYR4 2012–2015
Fluoride
320 µg/L 8%
of the EPA limit 4000 µg/L
2/6 SYR4 2012–2015
Chromium
1 µg/L 1%
of the EPA limit 100 µg/L
1/6 SYR4 2012–2015
Dichloromethane
2.7 µg/L 54%
of the EPA limit 5 µg/L
1/32 SYR4 2012–2015
Monobromoacetic Acid
1 µg/L
No EPA limit set
1/4 SYR4 2012–2015
Monochloroacetic Acid
1 µg/L
No EPA limit set
1/4 SYR4 2012–2015
Trichloroacetic Acid
1 µg/L
No EPA limit set
1/4 SYR4 2012–2015
27 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-DichloropropaneAntimony, TotalArsenicBenzeneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbon TetrachlorideEthylbenzeneMercurySeleniumStyreneTetrachloroethyleneThallium, TotalTolueneTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
LIBERTY UTILITIES

Frequently asked questions about Mount Ebo Ws

Is Mount Ebo Ws tap water safe to drink?

EPA monitoring detected 18 contaminants in Mount Ebo Ws's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Mount Ebo Ws's water?

EPA monitoring detected Nitrate, Barium, Chloroform, Bromodichloromethane, Lead, and others. The full list with the level and data source for each is above.

How many people does Mount Ebo Ws serve?

Mount Ebo Ws reports serving 1,500 people in New York, per its EPA record.

Has Mount Ebo Ws had any water quality violations?

The EPA has 2 violations on file for Mount Ebo Ws, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.