← New York

Tap water quality report

Middlebranch Apts

EPA monitoring tested this supplier for 46 contaminants and detected 17. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

46
contaminants tested
17
detected
50
people served
0
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Putnam

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

0
health-based violations
17
violations on file
0
still open
ViolationTypeStatusPeriod
MON Monitoring Resolved 2020-03-01 → 2020-03-31
MON Monitoring Resolved 2020-03-01 → 2020-03-31
MR Monitoring Resolved 2013-03-01 → 2013-03-31
MR Monitoring Resolved 2013-03-01 → 2013-03-31
MR Monitoring Resolved 2013-03-01 → 2013-03-31
MR Monitoring Resolved 2009-05-01 → 2009-05-31
MR Monitoring Resolved 2009-05-01 → 2009-05-31
MR Monitoring Resolved 2009-05-01 → 2009-05-31
MR Monitoring Resolved 2003-09-01 → 2003-09-30
MR Monitoring Resolved 2003-09-01 → 2003-09-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the single worst sample on record — over 100% is worth reading, but is not by itself a violation. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
2930 µg/L 29%
of the EPA limit 10000 µg/L
8/8 SYR4 2013–2017
Lead
0.00060 mg/L 4%
of the EPA limit 0.0150 mg/L
5/5 LCR 2021
Dibromochloromethane
8.6 µg/L
No EPA limit set
4/8 SYR4 2012–2019
Barium
367 µg/L 18%
of the EPA limit 2000 µg/L
3/3 SYR4 2013–2019
Bromodichloromethane
6 µg/L
No EPA limit set
3/8 SYR4 2012–2019
Chloroform
3.1 µg/L
No EPA limit set
3/8 SYR4 2012–2019
Bromoform
2.3 µg/L
No EPA limit set
2/7 SYR4 2012–2019
Dibromoacetic Acid
4.5 µg/L
No EPA limit set
2/6 SYR4 2012–2019
Dichloroacetic Acid
2.5 µg/L
No EPA limit set
2/6 SYR4 2012–2019
Fluoride
2200 µg/L 55%
of the EPA limit 4000 µg/L
2/2 SYR4 2016–2019
TTHM
20 µg/L 25%
of the EPA limit 80 µg/L
2/5 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
9.3 µg/L 16%
of the EPA limit 60 µg/L
2/5 SYR4 2012–2019
Trichloroacetic Acid
2.3 µg/L
No EPA limit set
2/6 SYR4 2012–2019
Arsenic
0.5000 µg/L 5%
of the EPA limit 10 µg/L
1/2 SYR4 2016–2019
Beryllium, Total
0.3000 µg/L 7.5%
of the EPA limit 4 µg/L
1/2 SYR4 2016–2019
Nitrate-Nitrite
2340 µg/L 23%
of the EPA limit 10000 µg/L
1/1 SYR4 2013
Selenium
1.6 µg/L 3.2%
of the EPA limit 50 µg/L
1/3 SYR4 2013–2019
29 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-DichloropropaneAntimony, TotalBenzeneChlorobenzeneCyanideCadmiumCarbon TetrachlorideChromiumDichloromethaneEthylbenzeneMercuryMonobromoacetic AcidMonochloroacetic AcidNitriteStyreneTetrachloroethyleneThallium, TotalTolueneTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
MIDDLEBRANCH LLC

Frequently asked questions about Middlebranch Apts

Is Middlebranch Apts tap water safe to drink?

EPA monitoring detected 17 contaminants in Middlebranch Apts's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Middlebranch Apts's water?

EPA monitoring detected Nitrate, Lead, Dibromochloromethane, Barium, Bromodichloromethane, and others. The full list with the level and data source for each is above.

How many people does Middlebranch Apts serve?

Middlebranch Apts reports serving 50 people in New York, per its EPA record.

Has Middlebranch Apts had any water quality violations?

The EPA has 17 violations on file for Middlebranch Apts, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.