← New York

Tap water quality report

Floyd Water District

EPA monitoring tested this supplier for 12 contaminants and detected 10. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

12
contaminants tested
10
detected
1,710
people served
12
health-based violations
Water source
SWP
Ownership
Local government
Counties served
Oneida

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

12
health-based violations
45
violations on file
2
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2022-01-01 → 2022-03-31
MCL Health-based Resolved 2022-01-01 → 2022-03-31
MCL Health-based Resolved 2022-01-01 → 2022-03-31
MCL Health-based Resolved 2021-10-01 → 2021-12-31
MCL Health-based Resolved 2021-10-01 → 2021-12-31
MCL Health-based Resolved 2021-10-01 → 2021-12-31
MCL Health-based Resolved 2021-07-01 → 2021-09-30
MCL Health-based Resolved 2021-07-01 → 2021-09-30
MCL Health-based Resolved 2021-07-01 → 2021-09-30
MCL Health-based Resolved 2012-09-01 → 2012-09-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the single worst sample on record — over 100% is worth reading, but is not by itself a violation. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Dichloroacetic Acid
35 µg/L
No EPA limit set
32/32 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
82 µg/L 137%
of the EPA limit, in the worst sample — 60 µg/L
32/32 SYR4 2012–2019
Bromodichloromethane
4.7 µg/L
No EPA limit set
31/32 SYR4 2012–2019
Chloroform
120 µg/L
No EPA limit set
31/32 SYR4 2012–2019
TTHM
124 µg/L 155%
of the EPA limit, in the worst sample — 80 µg/L
31/32 SYR4 2012–2019
Trichloroacetic Acid
51.8 µg/L
No EPA limit set
31/32 SYR4 2012–2019
Monochloroacetic Acid
8.04 µg/L
No EPA limit set
15/32 SYR4 2012–2019
Lead
0.0010 mg/L 6.7%
of the EPA limit 0.0150 mg/L
9/9 LCR 2024
Dibromoacetic Acid
2.8 µg/L
No EPA limit set
3/32 SYR4 2012–2019
Monobromoacetic Acid
2.3 µg/L
No EPA limit set
3/32 SYR4 2012–2019
2 contaminants tested, none detected
BromoformDibromochloromethane

Utility contact

Contact
SUPERVISOR, TOWN
Phone
315-865-4256
Email
tofloydw@dreamscape.com

Frequently asked questions about Floyd Water District

Is Floyd Water District tap water safe to drink?

EPA monitoring detected 10 contaminants in Floyd Water District's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Floyd Water District's water?

EPA monitoring detected Dichloroacetic Acid, Total Haloacetic Acids (HAA5), Bromodichloromethane, Chloroform, TTHM, and others. The full list with the level and data source for each is above.

How many people does Floyd Water District serve?

Floyd Water District reports serving 1,710 people in New York, per its EPA record.

Has Floyd Water District had any water quality violations?

The EPA has 45 violations on file for Floyd Water District, of which 12 are health-based (a contaminant limit or required treatment was breached) and 2 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.