Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2000-01-01 → 2000-01-31 |
| MCL | Health-based | Resolved | 2000-01-01 → 2000-01-31 |
| Other | Monitoring | Resolved | 2002-02-01 → 2002-02-28 |
| Other | Monitoring | Resolved | 2002-02-01 → 2002-02-28 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 4150 µg/L 42% of the EPA limit 10000 µg/L
worst single sample: 4530 µg/L | 44/44 | SYR4 | 2012–2019 |
| Barium | 33.05 µg/L 1.7% of the EPA limit 2000 µg/L
worst single sample: 34 µg/L | 20/22 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 4188 µg/L 42% of the EPA limit 10000 µg/L
worst single sample: 4530 µg/L | 19/19 | SYR4 | 2012–2018 |
| Lead | 0.0021 mg/L 14% of the EPA limit 0.0150 mg/L | 14/14 | LCR | 2025 |
| Lead | 4.97 µg/L 33% of the EPA limit 15 µg/L
worst single sample: 5.94 µg/L | 11/20 | SYR4 | 2012–2019 |
| Copper | 25.1 µg/L 1.9% of the EPA limit 1300 µg/L
worst single sample: 26 µg/L | 7/21 | SYR4 | 2012–2019 |
| Combined Radium (-226 And -228) | 3.471 pCi/L 69% of the EPA limit 5 pCi/L
worst single sample: 3.6 pCi/L | 4/6 | SYR4 | 2013–2016 |
| Combined Uranium | 0.7570 µg/L 2.5% of the EPA limit 30 µg/L
worst single sample: 0.8050 µg/L | 3/3 | SYR4 | 2013 |
| Gross Beta Particle Activity | 2.552 pCi/L No EPA limit set
worst single sample: 2.73 pCi/L | 3/3 | SYR4 | 2016 |
| Dibromochloromethane | 2.24 µg/L No EPA limit set
worst single sample: 2.3 µg/L | 2/7 | SYR4 | 2014–2019 |
| Fluoride | 138 µg/L 3.5% of the EPA limit 4000 µg/L
worst single sample: 140 µg/L | 2/22 | SYR4 | 2012–2019 |
| Bromodichloromethane | 0.9800 µg/L No EPA limit set | 1/7 | SYR4 | 2014–2019 |
| Chloroform | 0.8300 µg/L No EPA limit set | 1/7 | SYR4 | 2014–2019 |
| Dibromoacetic Acid | 0.9200 µg/L No EPA limit set | 1/7 | SYR4 | 2014–2019 |
| Dichloroacetic Acid | 1.24 µg/L No EPA limit set | 1/7 | SYR4 | 2014–2019 |
97 contaminants tested, none detected
Utility contact
Frequently asked questions about Farmingdale
Is Farmingdale tap water safe to drink?
EPA monitoring detected 15 contaminants in Farmingdale's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Farmingdale's water?
EPA monitoring detected Nitrate, Barium, Nitrate-Nitrite, Lead, Lead, and others. The full list with the level and data source for each is above.
How many people does Farmingdale serve?
Farmingdale reports serving 8,744 people in New York, per its EPA record.
Has Farmingdale had any water quality violations?
The EPA has 4 violations on file for Farmingdale, of which 2 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.