← New York

Tap water quality report

Halcottsville Water District No. 1

EPA monitoring tested this supplier for 42 contaminants and detected 14. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

42
contaminants tested
14
detected
48
people served
4
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Delaware

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

4
health-based violations
124
violations on file
3
still open
ViolationTypeStatusPeriod
MCL Health-based Archived 1996-01-01 → 1996-01-31
MCL Health-based Archived 1993-09-01 → 1993-09-30
MCL Health-based Archived 1993-09-01 → 1993-09-30
TT Health-based Resolved 1992-01-01
Other Monitoring Unaddressed 2025-09-02
MON Monitoring Resolved 2025-07-01 → 2025-07-31
MON Monitoring Resolved 2025-07-01 → 2025-07-31
MON Monitoring Resolved 2025-07-01 → 2025-07-31
MR Monitoring Archived 2025-01-01 → 2025-12-31
MR Monitoring Archived 2025-01-01 → 2025-12-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Lead
0.0118 mg/L 79%
of the EPA limit 0.0150 mg/L
20/20 LCR 2025
Nitrate
680 µg/L 6.8%
of the EPA limit 10000 µg/L
12/16 SYR4 2012–2019
Arsenic
9.8 µg/L 98%
of the EPA limit 10 µg/L
worst single sample: 10.1 µg/L
7/7 SYR4 2012–2019
TTHM
58.896 µg/L 74%
of the EPA limit 80 µg/L
worst single sample: 66.12 µg/L
5/5 SYR4 2013–2019
Total Haloacetic Acids (HAA5)
13.12 µg/L 22%
of the EPA limit 60 µg/L
worst single sample: 13.6 µg/L
5/5 SYR4 2013–2019
Barium
148.3 µg/L 7.4%
of the EPA limit 2000 µg/L
worst single sample: 151 µg/L
3/3 SYR4 2012–2018
Fluoride
129.5 µg/L 3.2%
of the EPA limit 4000 µg/L
worst single sample: 130 µg/L
2/3 SYR4 2012–2018
Bromodichloromethane
1.6 µg/L
No EPA limit set
1/1 SYR4 2013
Bromoform
21 µg/L
No EPA limit set
1/1 SYR4 2013
Chloroform
0.7500 µg/L
No EPA limit set
1/1 SYR4 2013
Dibromoacetic Acid
6.8 µg/L
No EPA limit set
1/1 SYR4 2013
Dibromochloromethane
6.6 µg/L
No EPA limit set
1/1 SYR4 2013
Dichloroacetic Acid
1 µg/L
No EPA limit set
1/1 SYR4 2013
Selenium
3 µg/L 6%
of the EPA limit 50 µg/L
1/3 SYR4 2012–2018
28 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-DichloropropaneAntimony, TotalBenzeneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbon TetrachlorideChromiumCombined Radium (-226 And -228)DichloromethaneEthylbenzeneMercuryStyreneTetrachloroethyleneThallium, TotalTolueneTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
MIDDLETOWN SUPERVISOR AND TOWN BOARD
Phone
845-586-2462
Email
middsuper@catskill.net

Frequently asked questions about Halcottsville Water District No. 1

Is Halcottsville Water District No. 1 tap water safe to drink?

EPA monitoring detected 14 contaminants in Halcottsville Water District No. 1's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Halcottsville Water District No. 1's water?

EPA monitoring detected Lead, Nitrate, Arsenic, TTHM, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.

How many people does Halcottsville Water District No. 1 serve?

Halcottsville Water District No. 1 reports serving 48 people in New York, per its EPA record.

Has Halcottsville Water District No. 1 had any water quality violations?

The EPA has 124 violations on file for Halcottsville Water District No. 1, of which 4 are health-based (a contaminant limit or required treatment was breached) and 3 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.