← New York

Tap water quality report

Homer Village-Newton Water Works

EPA monitoring tested this supplier for 102 contaminants and detected 17. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

102
contaminants tested
17
detected
4,368
people served
4
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Cortland

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

4
health-based violations
407
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 1994-08-01 → 1994-08-31
MCL Health-based Resolved 1994-08-01 → 1994-08-31
MCL Health-based Resolved 1994-08-01 → 1994-08-31
MCL Health-based Archived 1993-12-01 → 1993-12-31
MR Monitoring Resolved 2020-01-01 → 2020-12-31
MR Monitoring Resolved 2020-01-01 → 2020-12-31
MR Monitoring Resolved 2020-01-01 → 2020-12-31
MR Monitoring Resolved 2020-01-01 → 2020-12-31
MR Monitoring Resolved 2020-01-01 → 2020-12-31
MR Monitoring Resolved 2020-01-01 → 2020-12-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the single worst sample on record — over 100% is worth reading, but is not by itself a violation. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
3660 µg/L 37%
of the EPA limit 10000 µg/L
30/32 SYR4 2012–2019
Nitrate-Nitrite
3660 µg/L 37%
of the EPA limit 10000 µg/L
16/16 SYR4 2012–2019
Bromodichloromethane
4.7 µg/L
No EPA limit set
13/13 SYR4 2013–2019
Dibromochloromethane
5.21 µg/L
No EPA limit set
13/13 SYR4 2013–2019
TTHM
15.76 µg/L 20%
of the EPA limit 80 µg/L
13/13 SYR4 2013–2019
Chloroform
4.11 µg/L
No EPA limit set
12/13 SYR4 2013–2019
Lead
0.0020 mg/L 13%
of the EPA limit 0.0150 mg/L
11/11 LCR 2025
Bromoform
4.84 µg/L
No EPA limit set
7/13 SYR4 2013–2019
Total Haloacetic Acids (HAA5)
2.86 µg/L 4.8%
of the EPA limit 60 µg/L
7/13 SYR4 2013–2019
Dibromoacetic Acid
2.2 µg/L
No EPA limit set
6/13 SYR4 2013–2019
Dichloroacetic Acid
1.3 µg/L
No EPA limit set
4/13 SYR4 2013–2019
Trichloroacetic Acid
1.35 µg/L
No EPA limit set
4/13 SYR4 2013–2019
Combined Radium (-226 And -228)
1.1 pCi/L 22%
of the EPA limit 5 pCi/L
3/3 SYR4 2013–2019
Barium
37.2 µg/L 1.9%
of the EPA limit 2000 µg/L
2/4 SYR4 2014–2017
Chromium
2.3 µg/L 2.3%
of the EPA limit 100 µg/L
2/4 SYR4 2014–2017
Di(2-ethylhexyl) Phthalate
1.4 µg/L 23%
of the EPA limit 6 µg/L
2/10 SYR4 2012–2016
Nitrite
2460 µg/L 246%
of the EPA limit, in the worst sample — 1000 µg/L
1/16 SYR4 2012–2019
85 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalArsenicAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneDichloromethaneDalaponDi(2-ethylhexyl) AdipateDinosebEthylene DibromideEndrinEthylbenzeneFluorideHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidNetfosaaNfdhaNmefosaaOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
WHITE, KEITH
Phone
607-749-2511
Email
kwhite@homerny.org

Frequently asked questions about Homer Village-Newton Water Works

Is Homer Village-Newton Water Works tap water safe to drink?

EPA monitoring detected 17 contaminants in Homer Village-Newton Water Works's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Homer Village-Newton Water Works's water?

EPA monitoring detected Nitrate, Nitrate-Nitrite, Bromodichloromethane, Dibromochloromethane, TTHM, and others. The full list with the level and data source for each is above.

How many people does Homer Village-Newton Water Works serve?

Homer Village-Newton Water Works reports serving 4,368 people in New York, per its EPA record.

Has Homer Village-Newton Water Works had any water quality violations?

The EPA has 407 violations on file for Homer Village-Newton Water Works, of which 4 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.