← New York

Tap water quality report

Bolivar-Richburg Water

EPA monitoring tested this supplier for 70 contaminants and detected 16. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

70
contaminants tested
16
detected
1,640
people served
0
health-based violations
Water source
Ground water under surface influence
Ownership
Local government
Counties served
Allegany

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

0
health-based violations
56
violations on file
0
still open
ViolationTypeStatusPeriod
MR Monitoring Resolved 2022-01-01 → 2022-12-31
MR Monitoring Resolved 2022-01-01 → 2022-12-31
MR Monitoring Resolved 2022-01-01 → 2022-12-31
MR Monitoring Resolved 2022-01-01 → 2022-12-31
MR Monitoring Resolved 2022-01-01 → 2022-12-31
MR Monitoring Resolved 2022-01-01 → 2022-12-31
MR Monitoring Resolved 2022-01-01 → 2022-12-31
MR Monitoring Resolved 2022-01-01 → 2022-12-31
MR Monitoring Resolved 2022-01-01 → 2022-12-31
MR Monitoring Resolved 2022-01-01 → 2022-12-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
TTHM
47.55 µg/L 59%
of the EPA limit 80 µg/L
worst single sample: 130 µg/L
18/18 SYR4 2017–2019
Total Haloacetic Acids (HAA5)
7.93 µg/L 13%
of the EPA limit 60 µg/L
worst single sample: 20 µg/L
18/18 SYR4 2017–2019
Lead
0.0012 mg/L 8%
of the EPA limit 0.0150 mg/L
14/14 LCR 2025
Bromoform
6.93 µg/L
No EPA limit set
worst single sample: 7 µg/L
8/8 SYR4 2019
Dibromochloromethane
5.815 µg/L
No EPA limit set
worst single sample: 6.9 µg/L
8/8 SYR4 2019
Dibromoacetic Acid
2.67 µg/L
No EPA limit set
worst single sample: 2.7 µg/L
7/8 SYR4 2019
Nitrate
410 µg/L 4.1%
of the EPA limit 10000 µg/L
6/8 SYR4 2018–2019
Bromodichloromethane
6.56 µg/L
No EPA limit set
worst single sample: 7.5 µg/L
5/8 SYR4 2019
Chloroform
10.68 µg/L
No EPA limit set
worst single sample: 12 µg/L
5/8 SYR4 2019
Barium
80.3 µg/L 4%
of the EPA limit 2000 µg/L
worst single sample: 86 µg/L
3/3 SYR4 2018–2019
Trichloroacetic Acid
1.84 µg/L
No EPA limit set
worst single sample: 1.9 µg/L
3/8 SYR4 2019
Dichloromethane
1.195 µg/L 24%
of the EPA limit 5 µg/L
worst single sample: 1.2 µg/L
2/9 SYR4 2018–2019
1,2-Dichloroethane
9.2 µg/L 184%
of the EPA limit, at the 95th percentile of samples — 5 µg/L
1/9 SYR4 2018–2019
Cyanide
57 µg/L 28%
of the EPA limit 200 µg/L
1/3 SYR4 2018–2019
Chromium
1.2 µg/L 1.2%
of the EPA limit 100 µg/L
1/3 SYR4 2018–2019
Dichloroacetic Acid
2.3 µg/L
No EPA limit set
1/8 SYR4 2019
54 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalArsenicAsbestosAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCadmiumCarbofuranCarbon TetrachlorideChlordaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebEthylene DibromideEndrinEthylbenzeneFluorideHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
DUNBAR, DYLAN S.
Phone
585-593-7220

Frequently asked questions about Bolivar-Richburg Water

Is Bolivar-Richburg Water tap water safe to drink?

EPA monitoring detected 16 contaminants in Bolivar-Richburg Water's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Bolivar-Richburg Water's water?

EPA monitoring detected TTHM, Total Haloacetic Acids (HAA5), Lead, Bromoform, Dibromochloromethane, and others. The full list with the level and data source for each is above.

How many people does Bolivar-Richburg Water serve?

Bolivar-Richburg Water reports serving 1,640 people in New York, per its EPA record.

Has Bolivar-Richburg Water had any water quality violations?

The EPA has 56 violations on file for Bolivar-Richburg Water, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.