Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MR | Monitoring | Resolved | 2022-01-01 → 2022-12-31 |
| MR | Monitoring | Resolved | 2022-01-01 → 2022-12-31 |
| MR | Monitoring | Resolved | 2022-01-01 → 2022-12-31 |
| MR | Monitoring | Resolved | 2022-01-01 → 2022-12-31 |
| MR | Monitoring | Resolved | 2022-01-01 → 2022-12-31 |
| MR | Monitoring | Resolved | 2022-01-01 → 2022-12-31 |
| MR | Monitoring | Resolved | 2022-01-01 → 2022-12-31 |
| MR | Monitoring | Resolved | 2022-01-01 → 2022-12-31 |
| MR | Monitoring | Resolved | 2022-01-01 → 2022-12-31 |
| MR | Monitoring | Resolved | 2022-01-01 → 2022-12-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| TTHM | 47.55 µg/L 59% of the EPA limit 80 µg/L
worst single sample: 130 µg/L | 18/18 | SYR4 | 2017–2019 |
| Total Haloacetic Acids (HAA5) | 7.93 µg/L 13% of the EPA limit 60 µg/L
worst single sample: 20 µg/L | 18/18 | SYR4 | 2017–2019 |
| Lead | 0.0012 mg/L 8% of the EPA limit 0.0150 mg/L | 14/14 | LCR | 2025 |
| Bromoform | 6.93 µg/L No EPA limit set
worst single sample: 7 µg/L | 8/8 | SYR4 | 2019 |
| Dibromochloromethane | 5.815 µg/L No EPA limit set
worst single sample: 6.9 µg/L | 8/8 | SYR4 | 2019 |
| Dibromoacetic Acid | 2.67 µg/L No EPA limit set
worst single sample: 2.7 µg/L | 7/8 | SYR4 | 2019 |
| Nitrate | 410 µg/L 4.1% of the EPA limit 10000 µg/L | 6/8 | SYR4 | 2018–2019 |
| Bromodichloromethane | 6.56 µg/L No EPA limit set
worst single sample: 7.5 µg/L | 5/8 | SYR4 | 2019 |
| Chloroform | 10.68 µg/L No EPA limit set
worst single sample: 12 µg/L | 5/8 | SYR4 | 2019 |
| Barium | 80.3 µg/L 4% of the EPA limit 2000 µg/L
worst single sample: 86 µg/L | 3/3 | SYR4 | 2018–2019 |
| Trichloroacetic Acid | 1.84 µg/L No EPA limit set
worst single sample: 1.9 µg/L | 3/8 | SYR4 | 2019 |
| Dichloromethane | 1.195 µg/L 24% of the EPA limit 5 µg/L
worst single sample: 1.2 µg/L | 2/9 | SYR4 | 2018–2019 |
| 1,2-Dichloroethane | 9.2 µg/L 184% of the EPA limit, at the 95th percentile of samples — 5 µg/L | 1/9 | SYR4 | 2018–2019 |
| Cyanide | 57 µg/L 28% of the EPA limit 200 µg/L | 1/3 | SYR4 | 2018–2019 |
| Chromium | 1.2 µg/L 1.2% of the EPA limit 100 µg/L | 1/3 | SYR4 | 2018–2019 |
| Dichloroacetic Acid | 2.3 µg/L No EPA limit set | 1/8 | SYR4 | 2019 |
54 contaminants tested, none detected
Utility contact
Frequently asked questions about Bolivar-Richburg Water
Is Bolivar-Richburg Water tap water safe to drink?
EPA monitoring detected 16 contaminants in Bolivar-Richburg Water's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Bolivar-Richburg Water's water?
EPA monitoring detected TTHM, Total Haloacetic Acids (HAA5), Lead, Bromoform, Dibromochloromethane, and others. The full list with the level and data source for each is above.
How many people does Bolivar-Richburg Water serve?
Bolivar-Richburg Water reports serving 1,640 people in New York, per its EPA record.
Has Bolivar-Richburg Water had any water quality violations?
The EPA has 56 violations on file for Bolivar-Richburg Water, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.