Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MR | Monitoring | Archived | 2023-01-01 → 2023-12-31 |
| MR | Monitoring | Archived | 2022-07-01 → 2023-12-31 |
| MR | Monitoring | Archived | 2022-07-01 → 2023-12-31 |
| MR | Monitoring | Archived | 2022-07-01 → 2023-12-31 |
| MR | Monitoring | Archived | 2022-07-01 → 2023-12-31 |
| MR | Monitoring | Archived | 2022-07-01 → 2023-12-31 |
| MR | Monitoring | Archived | 2022-07-01 → 2023-12-31 |
| MR | Monitoring | Archived | 2022-07-01 → 2023-12-31 |
| MR | Monitoring | Archived | 2022-07-01 → 2023-12-31 |
| MR | Monitoring | Archived | 2022-07-01 → 2023-12-31 |
PFAS detected
| Contaminant | Max | Detection rate | Period |
|---|---|---|---|
| Pfba | 0.0052 µg/L | 1/4 | 2023 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Fluoride | 1100 µg/L 28% of the EPA limit 4000 µg/L
worst single sample: 1200 µg/L | 92/92 | SYR4 | 2012–2019 |
| TTHM | 97.6 µg/L 122% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 109 µg/L | 47/47 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 62.7 µg/L 105% of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 81 µg/L | 47/47 | SYR4 | 2012–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 20/20 | LCR | 2025 |
| Nitrate | 1500 µg/L 15% of the EPA limit 10000 µg/L | 14/16 | SYR4 | 2012–2019 |
| Chloroform | 50.55 µg/L No EPA limit set
worst single sample: 51 µg/L | 10/10 | SYR4 | 2012–2019 |
| Dibromochloromethane | 5.9865 µg/L No EPA limit set
worst single sample: 6.45 µg/L | 10/10 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 23.65 µg/L No EPA limit set
worst single sample: 25 µg/L | 10/10 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 31.55 µg/L No EPA limit set
worst single sample: 32 µg/L | 10/10 | SYR4 | 2012–2019 |
| Bromodichloromethane | 19.2 µg/L No EPA limit set
worst single sample: 21 µg/L | 9/10 | SYR4 | 2012–2019 |
| Barium | 47.8 µg/L 2.4% of the EPA limit 2000 µg/L
worst single sample: 49 µg/L | 7/7 | SYR4 | 2012–2019 |
| Arsenic | 7 µg/L 70% of the EPA limit 10 µg/L | 1/8 | SYR4 | 2012–2019 |
| Combined Radium (-226 And -228) | 1.59 pCi/L 32% of the EPA limit 5 pCi/L | 1/1 | SYR4 | 2016 |
| Combined Uranium | 0.0570 µg/L 0.2% of the EPA limit 30 µg/L | 1/1 | SYR4 | 2016 |
| Dibromoacetic Acid | 0.5400 µg/L No EPA limit set | 1/10 | SYR4 | 2012–2019 |
| Gross Beta Particle Activity | 0.5770 pCi/L No EPA limit set | 1/1 | SYR4 | 2016 |
| Nitrate-Nitrite | 1480 µg/L 15% of the EPA limit 10000 µg/L | 1/1 | SYR4 | 2016 |
87 contaminants tested, none detected
Utility contact
Frequently asked questions about Wellsville Village Public Water
Is Wellsville Village Public Water tap water safe to drink?
EPA monitoring detected 18 contaminants in Wellsville Village Public Water's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Wellsville Village Public Water's water?
EPA monitoring detected Fluoride, TTHM, Total Haloacetic Acids (HAA5), Lead, Nitrate, and others. The full list with the level and data source for each is above.
How many people does Wellsville Village Public Water serve?
Wellsville Village Public Water reports serving 5,700 people in New York, per its EPA record.
Has Wellsville Village Public Water had any water quality violations?
The EPA has 30 violations on file for Wellsville Village Public Water, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.